⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 300 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.11%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.83V (3.68%)
Voltage at Load End237.3 VLoss: 2.67 V (3707.4 W)
Power & Breaker (125%)332.55 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 300 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1303.58 V (543.16%)0.0 V2150.3 V (895.96%)1806291.7 WDrop/Amp High
12 AWG3.31 mm²20 A819.17 V (341.32%)0.0 V1351.24 V (563.02%)1135071.5 WDrop/Amp High
10 AWG5.26 mm²30 A515.48 V (214.78%)0.0 V850.31 V (354.29%)714275.0 WDrop/Amp High
8 AWG8.37 mm²50 A323.95 V (134.98%)0.0 V534.36 V (222.65%)448875.4 WDrop/Amp High
6 AWG13.3 mm²65 A203.87 V (84.94%)36.1 V336.29 V (140.12%)282487.7 WDrop/Amp High
4 AWG21.15 mm²85 A128.2 V (53.42%)111.8 V211.47 V (88.11%)177640.0 WDrop/Amp High
3 AWG26.67 mm²100 A101.67 V (42.36%)138.3 V167.7 V (69.88%)140873.1 WDrop/Amp High
2 AWG33.62 mm²115 A80.65 V (33.6%)159.4 V133.03 V (55.43%)111751.5 WDrop/Amp High
1 AWG42.41 mm²130 A63.93 V (26.64%)176.1 V105.46 V (43.94%)88589.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A50.69 V (21.12%)189.3 V83.62 V (34.84%)70239.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A40.21 V (16.75%)199.8 V66.33 V (27.64%)55718.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A31.9 V (13.29%)208.1 V52.61 V (21.92%)44195.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.29 V (10.54%)214.7 V41.72 V (17.38%)35047.5 WDrop/Amp High
250 kcmil126.7 mm²255 A21.4 V (8.92%)218.6 V35.3 V (14.71%)29653.4 WDrop/Amp High
300 kcmil152.0 mm²285 A17.84 V (7.43%)222.2 V29.43 V (12.26%)24717.7 WDrop/Amp High
350 kcmil177.3 mm²310 A15.29 V (6.37%)224.7 V25.23 V (10.51%)21190.6 WDrop/Amp High
400 kcmil202.7 mm²335 A13.38 V (5.57%)226.6 V22.07 V (9.19%)18535.2 WDrop/Amp High
500 kcmil253.4 mm²380 A10.7 V (4.46%)229.3 V17.65 V (7.35%)14826.7 WDrop/Amp High
600 kcmil304.0 mm²420 A8.92 V (3.72%)231.1 V14.71 V (6.13%)12358.8 WDrop/Amp High
750 kcmil380.0 mm²475 A7.14 V (2.97%)232.9 V11.77 V (4.9%)9887.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.35 V (2.23%)234.6 V8.83 V (3.68%)7414.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 300 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 300 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.67V (1.11%) and delivers 237.3V at the load.

What size aluminum wire is required for 800 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.83V (3.68%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.