⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.07V (10.61%)
Voltage at Load End203.5 VLoss: 4.46 V (6179.0 W)
Power & Breaker (125%)288.21 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3258.95 V (1566.8%)0.0 V5375.74 V (2584.49%)4515729.2 WDrop/Amp High
12 AWG3.31 mm²20 A2047.92 V (984.58%)0.0 V3378.11 V (1624.09%)2837678.8 WDrop/Amp High
10 AWG5.26 mm²30 A1288.71 V (619.57%)0.0 V2125.77 V (1022.0%)1785687.6 WDrop/Amp High
8 AWG8.37 mm²50 A809.87 V (389.36%)0.0 V1335.91 V (642.26%)1122188.4 WDrop/Amp High
6 AWG13.3 mm²65 A509.67 V (245.03%)0.0 V840.72 V (404.19%)706219.3 WDrop/Amp High
4 AWG21.15 mm²85 A320.5 V (154.09%)0.0 V528.68 V (254.17%)444100.1 WDrop/Amp High
3 AWG26.67 mm²100 A254.17 V (122.2%)0.0 V419.26 V (201.57%)352182.9 WDrop/Amp High
2 AWG33.62 mm²115 A201.62 V (96.93%)6.4 V332.59 V (159.9%)279378.8 WDrop/Amp High
1 AWG42.41 mm²130 A159.84 V (76.84%)48.2 V263.65 V (126.76%)221474.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A126.73 V (60.93%)81.3 V209.04 V (100.5%)175597.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A100.53 V (48.33%)107.5 V165.82 V (79.72%)139295.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A79.74 V (38.34%)128.3 V131.53 V (63.24%)110489.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A63.23 V (30.4%)144.8 V104.31 V (50.15%)87618.6 WDrop/Amp High
250 kcmil126.7 mm²255 A53.5 V (25.72%)154.5 V88.25 V (42.43%)74133.5 WDrop/Amp High
300 kcmil152.0 mm²285 A44.6 V (21.44%)163.4 V73.56 V (35.37%)61794.2 WDrop/Amp High
350 kcmil177.3 mm²310 A38.23 V (18.38%)169.8 V63.07 V (30.32%)52976.4 WDrop/Amp High
400 kcmil202.7 mm²335 A33.44 V (16.08%)174.6 V55.16 V (26.52%)46338.0 WDrop/Amp High
500 kcmil253.4 mm²380 A26.75 V (12.86%)181.2 V44.13 V (21.21%)37066.8 WDrop/Amp High
600 kcmil304.0 mm²420 A22.3 V (10.72%)185.7 V36.78 V (17.68%)30897.1 WDrop/Amp High
750 kcmil380.0 mm²475 A17.84 V (8.58%)190.2 V29.43 V (14.15%)24717.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.38 V (6.43%)194.6 V22.07 V (10.61%)18537.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 750 feet one-way at 208V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.46V (2.14%) and delivers 203.5V at the load.

What size aluminum wire is required for 800 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.07V (10.61%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.