⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.84%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.79V (2.78%)
Voltage at Load End206.2 VLoss: 1.75 V (2737.1 W)
Power & Breaker (125%)324.24 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A855.47 V (411.29%)0.0 V1411.13 V (678.43%)1333551.3 WDrop/Amp High
12 AWG3.31 mm²20 A537.58 V (258.45%)0.0 V886.75 V (426.32%)838002.0 WDrop/Amp High
10 AWG5.26 mm²30 A338.29 V (162.64%)0.0 V558.01 V (268.28%)527335.9 WDrop/Amp High
8 AWG8.37 mm²50 A212.59 V (102.21%)0.0 V350.68 V (168.59%)331396.3 WDrop/Amp High
6 AWG13.3 mm²65 A133.79 V (64.32%)74.2 V220.69 V (106.1%)208555.4 WDrop/Amp High
4 AWG21.15 mm²85 A84.13 V (40.45%)123.9 V138.78 V (66.72%)131148.3 WDrop/Amp High
3 AWG26.67 mm²100 A66.72 V (32.08%)141.3 V110.05 V (52.91%)104004.0 WDrop/Amp High
2 AWG33.62 mm²115 A52.93 V (25.45%)155.1 V87.3 V (41.97%)82504.1 WDrop/Amp High
1 AWG42.41 mm²130 A41.96 V (20.17%)166.0 V69.21 V (33.27%)65404.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A33.27 V (15.99%)174.7 V54.87 V (26.38%)51856.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.39 V (12.69%)181.6 V43.53 V (20.93%)41135.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.93 V (10.06%)187.1 V34.53 V (16.6%)32628.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.6 V (7.98%)191.4 V27.38 V (13.16%)25874.9 WDrop/Amp High
250 kcmil126.7 mm²255 A14.04 V (6.75%)194.0 V23.17 V (11.14%)21892.6 WDrop/Amp High
300 kcmil152.0 mm²285 A11.71 V (5.63%)196.3 V19.31 V (9.28%)18248.6 WDrop/Amp High
350 kcmil177.3 mm²310 A10.04 V (4.83%)198.0 V16.55 V (7.96%)15644.6 WDrop/Amp High
400 kcmil202.7 mm²335 A8.78 V (4.22%)199.2 V14.48 V (6.96%)13684.2 WDrop/Amp High
500 kcmil253.4 mm²380 A7.02 V (3.38%)201.0 V11.58 V (5.57%)10946.3 WDrop/Amp High
600 kcmil304.0 mm²420 A5.85 V (2.81%)202.1 V9.66 V (4.64%)9124.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.68 V (2.25%)203.3 V7.72 V (3.71%)7299.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.51 V (1.69%)204.5 V5.79 V (2.78%)5474.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 175 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.75V (0.84%) and delivers 206.2V at the load.

What size aluminum wire is required for 900 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.79V (2.78%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.