🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.86V (9.55%)
Voltage at Load End202.0 VLoss: 6.02 V (9384.4 W)
Power & Breaker (125%)324.24 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2933.05 V (1410.12%)0.0 V4838.17 V (2326.04%)4572175.8 WDrop/Amp High
12 AWG3.31 mm²20 A1843.13 V (886.12%)0.0 V3040.3 V (1461.68%)2873149.8 WDrop/Amp High
10 AWG5.26 mm²30 A1159.84 V (557.61%)0.0 V1913.19 V (919.8%)1808008.7 WDrop/Amp High
8 AWG8.37 mm²50 A728.88 V (350.42%)0.0 V1202.32 V (578.04%)1136215.7 WDrop/Amp High
6 AWG13.3 mm²65 A458.7 V (220.53%)0.0 V756.65 V (363.77%)715047.0 WDrop/Amp High
4 AWG21.15 mm²85 A288.45 V (138.68%)0.0 V475.81 V (228.75%)449651.3 WDrop/Amp High
3 AWG26.67 mm²100 A228.75 V (109.98%)0.0 V377.33 V (181.41%)356585.1 WDrop/Amp High
2 AWG33.62 mm²115 A181.46 V (87.24%)26.5 V299.33 V (143.91%)282871.1 WDrop/Amp High
1 AWG42.41 mm²130 A143.85 V (69.16%)64.1 V237.29 V (114.08%)224242.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A114.05 V (54.83%)93.9 V188.14 V (90.45%)177792.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A90.48 V (43.5%)117.5 V149.24 V (71.75%)141037.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A71.77 V (34.5%)136.2 V118.38 V (56.91%)111870.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A56.91 V (27.36%)151.1 V93.87 V (45.13%)88713.9 WDrop/Amp High
250 kcmil126.7 mm²255 A48.15 V (23.15%)159.8 V79.43 V (38.19%)75060.2 WDrop/Amp High
300 kcmil152.0 mm²285 A40.14 V (19.3%)167.9 V66.21 V (31.83%)62566.6 WDrop/Amp High
350 kcmil177.3 mm²310 A34.41 V (16.54%)173.6 V56.76 V (27.29%)53638.6 WDrop/Amp High
400 kcmil202.7 mm²335 A30.1 V (14.47%)177.9 V49.65 V (23.87%)46917.2 WDrop/Amp High
500 kcmil253.4 mm²380 A24.08 V (11.57%)183.9 V39.71 V (19.09%)37530.1 WDrop/Amp High
600 kcmil304.0 mm²420 A20.07 V (9.65%)187.9 V33.1 V (15.92%)31283.3 WDrop/Amp High
750 kcmil380.0 mm²475 A16.05 V (7.72%)191.9 V26.48 V (12.73%)25026.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.04 V (5.79%)196.0 V19.86 V (9.55%)18768.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 600 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.02V (2.9%) and delivers 202.0V at the load.

What size aluminum wire is required for 900 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.86V (9.55%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.