125 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 6.88V (2.99%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.67V (2.47%)
Voltage at Load223.1 VLine Loss: 859.8 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A160.5 V (69.78%)69.5 V264.75 V (115.11%)20062.5 WDrop High
2.5 mm²24 A18 A96.3 V (41.87%)133.7 V158.85 V (69.07%)12037.5 WDrop High
4 mm²32 A25 A60.19 V (26.17%)169.8 V99.28 V (43.17%)7523.4 WDrop High
6 mm²41 A32 A40.12 V (17.45%)189.9 V66.19 V (28.78%)5015.6 WDrop High
10 mm²57 A44 A24.07 V (10.47%)205.9 V39.71 V (17.27%)3009.4 WDrop High
16 mm²76 A59 A15.05 V (6.54%)215.0 V24.82 V (10.79%)1880.9 WDrop High
25 mm²101 A78 A9.63 V (4.19%)220.4 V15.88 V (6.91%)1203.8 WDrop High
35 mm²125 A97 A6.88 V (2.99%)223.1 V11.35 V (4.93%)859.8 W✓ OK (≤3%)
50 mm²151 A118 A4.81 V (2.09%)225.2 V7.94 V (3.45%)601.9 W✓ OK (≤3%)
70 mm²192 A150 A3.44 V (1.5%)226.6 V5.67 V (2.47%)429.9 W✓ OK (≤3%)
95 mm²232 A181 A2.53 V (1.1%)227.5 V4.18 V (1.82%)316.8 W✓ OK (≤3%)
120 mm²269 A210 A2.01 V (0.87%)228.0 V3.31 V (1.44%)250.8 W✓ OK (≤3%)
150 mm²309 A241 A1.6 V (0.7%)228.4 V2.65 V (1.15%)200.6 W✓ OK (≤3%)
185 mm²353 A275 A1.3 V (0.57%)228.7 V2.15 V (0.93%)162.7 W✓ OK (≤3%)
240 mm²415 A324 A1.0 V (0.44%)229.0 V1.65 V (0.72%)125.4 W✓ OK (≤3%)
300 mm²477 A372 A0.8 V (0.35%)229.2 V1.32 V (0.58%)100.3 W✓ OK (≤3%)
400 mm²570 A445 A0.6 V (0.26%)229.4 V0.99 V (0.43%)75.2 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 125A at 45 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 45m at 230V (voltage drop: 6.88V or 2.99%).

What is the power capacity of 125A at 230V?

At unity power factor, 125A at 230V supports 28.75 kW with a standard 125A circuit breaker.