125 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.25V (2.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.54V (3.22%)
Voltage at Load46.8 VLine Loss: 156.0 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A249.67 V (520.14%)0.0 V411.83 V (857.99%)31208.3 WDrop High
2.5 mm²24 A18 A149.8 V (312.08%)0.0 V247.1 V (514.79%)18725.0 WDrop High
4 mm²32 A25 A93.62 V (195.05%)0.0 V154.44 V (321.74%)11703.1 WDrop High
6 mm²41 A32 A62.42 V (130.03%)0.0 V102.96 V (214.5%)7802.1 WDrop High
10 mm²57 A44 A37.45 V (78.02%)10.6 V61.78 V (128.7%)4681.2 WDrop High
16 mm²76 A59 A23.41 V (48.76%)24.6 V38.61 V (80.44%)2925.8 WDrop High
25 mm²101 A78 A14.98 V (31.21%)33.0 V24.71 V (51.48%)1872.5 WDrop High
35 mm²125 A97 A10.7 V (22.29%)37.3 V17.65 V (36.77%)1337.5 WDrop High
50 mm²151 A118 A7.49 V (15.6%)40.5 V12.36 V (25.74%)936.2 WDrop High
70 mm²192 A150 A5.35 V (11.15%)42.6 V8.82 V (18.39%)668.8 WDrop High
95 mm²232 A181 A3.94 V (8.21%)44.1 V6.5 V (13.55%)492.8 WDrop High
120 mm²269 A210 A3.12 V (6.5%)44.9 V5.15 V (10.72%)390.1 WDrop High
150 mm²309 A241 A2.5 V (5.2%)45.5 V4.12 V (8.58%)312.1 WDrop High
185 mm²353 A275 A2.02 V (4.22%)46.0 V3.34 V (6.96%)253.0 W~ ≤5%
240 mm²415 A324 A1.56 V (3.25%)46.4 V2.57 V (5.36%)195.1 W~ ≤5%
300 mm²477 A372 A1.25 V (2.6%)46.8 V2.06 V (4.29%)156.0 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (1.95%)47.1 V1.54 V (3.22%)117.0 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 70 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 125A over 70m at 48V (voltage drop: 1.25V or 2.6%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.