100 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 2.97V (0.43%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 2.45V (0.35%)
Voltage at Load687.0 VLine Loss: 513.6 W
Max Power & Breaker119.51 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.42 V (7.16%)640.6 V81.52 V (11.81%)8560.0 WDrop High
2.5 mm²24 A18 A29.65 V (4.3%)660.3 V48.91 V (7.09%)5136.0 WDrop High
4 mm²32 A25 A18.53 V (2.69%)671.5 V30.57 V (4.43%)3210.0 WDrop High
6 mm²41 A32 A12.36 V (1.79%)677.6 V20.38 V (2.95%)2140.0 WDrop High
10 mm²57 A44 A7.41 V (1.07%)682.6 V12.23 V (1.77%)1284.0 WDrop High
16 mm²76 A59 A4.63 V (0.67%)685.4 V7.64 V (1.11%)802.5 WDrop High
25 mm²101 A78 A2.97 V (0.43%)687.0 V4.89 V (0.71%)513.6 W✓ OK (≤3%)
35 mm²125 A97 A2.12 V (0.31%)687.9 V3.49 V (0.51%)366.9 W✓ OK (≤3%)
50 mm²151 A118 A1.48 V (0.21%)688.5 V2.45 V (0.35%)256.8 W✓ OK (≤3%)
70 mm²192 A150 A1.06 V (0.15%)688.9 V1.75 V (0.25%)183.4 W✓ OK (≤3%)
95 mm²232 A181 A0.78 V (0.11%)689.2 V1.29 V (0.19%)135.2 W✓ OK (≤3%)
120 mm²269 A210 A0.62 V (0.09%)689.4 V1.02 V (0.15%)107.0 W✓ OK (≤3%)
150 mm²309 A241 A0.49 V (0.07%)689.5 V0.82 V (0.12%)85.6 W✓ OK (≤3%)
185 mm²353 A275 A0.4 V (0.06%)689.6 V0.66 V (0.1%)69.4 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.04%)689.7 V0.51 V (0.07%)53.5 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.04%)689.8 V0.41 V (0.06%)42.8 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.03%)689.8 V0.31 V (0.04%)32.1 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 100A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 100A over 20m at 690V (voltage drop: 2.97V or 0.43%).

What is the power capacity of 100A at 690V?

At unity power factor, 100A at 690V supports 119.51 kW with a standard 100A circuit breaker.