125 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 2.65V (0.38%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 2.18V (0.32%)
Voltage at Load687.4 VLine Loss: 573.2 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (8.95%)628.2 V101.9 V (14.77%)13375.0 WDrop High
2.5 mm²24 A18 A37.07 V (5.37%)652.9 V61.14 V (8.86%)8025.0 WDrop High
4 mm²32 A25 A23.17 V (3.36%)666.8 V38.21 V (5.54%)5015.6 WDrop High
6 mm²41 A32 A15.44 V (2.24%)674.6 V25.48 V (3.69%)3343.8 WDrop High
10 mm²57 A44 A9.27 V (1.34%)680.7 V15.29 V (2.22%)2006.2 WDrop High
16 mm²76 A59 A5.79 V (0.84%)684.2 V9.55 V (1.38%)1253.9 WDrop High
25 mm²101 A78 A3.71 V (0.54%)686.3 V6.11 V (0.89%)802.5 WDrop High
35 mm²125 A97 A2.65 V (0.38%)687.4 V4.37 V (0.63%)573.2 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.27%)688.1 V3.06 V (0.44%)401.2 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.19%)688.7 V2.18 V (0.32%)286.6 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.14%)689.0 V1.61 V (0.23%)211.2 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.11%)689.2 V1.27 V (0.18%)167.2 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.09%)689.4 V1.02 V (0.15%)133.8 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.07%)689.5 V0.83 V (0.12%)108.4 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.06%)689.6 V0.64 V (0.09%)83.6 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.04%)689.7 V0.51 V (0.07%)66.9 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.03%)689.8 V0.38 V (0.06%)50.2 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 20m at 690V (voltage drop: 2.65V or 0.38%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.