32 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 5.93V (0.86%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 6.52V (0.95%)
Voltage at Load684.1 VLine Loss: 328.7 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.81 V (2.29%)674.2 V26.09 V (3.78%)876.5 WDrop High
2.5 mm²24 A18 A9.49 V (1.38%)680.5 V15.65 V (2.27%)525.9 WDrop High
4 mm²32 A25 A5.93 V (0.86%)684.1 V9.78 V (1.42%)328.7 W✓ OK (≤3%)
6 mm²41 A32 A3.95 V (0.57%)686.0 V6.52 V (0.95%)219.1 W✓ OK (≤3%)
10 mm²57 A44 A2.37 V (0.34%)687.6 V3.91 V (0.57%)131.5 W✓ OK (≤3%)
16 mm²76 A59 A1.48 V (0.21%)688.5 V2.45 V (0.35%)82.2 W✓ OK (≤3%)
25 mm²101 A78 A0.95 V (0.14%)689.1 V1.57 V (0.23%)52.6 W✓ OK (≤3%)
35 mm²125 A97 A0.68 V (0.1%)689.3 V1.12 V (0.16%)37.6 W✓ OK (≤3%)
50 mm²151 A118 A0.47 V (0.07%)689.5 V0.78 V (0.11%)26.3 W✓ OK (≤3%)
70 mm²192 A150 A0.34 V (0.05%)689.7 V0.56 V (0.08%)18.8 W✓ OK (≤3%)
95 mm²232 A181 A0.25 V (0.04%)689.8 V0.41 V (0.06%)13.8 W✓ OK (≤3%)
120 mm²269 A210 A0.2 V (0.03%)689.8 V0.33 V (0.05%)11.0 W✓ OK (≤3%)
150 mm²309 A241 A0.16 V (0.02%)689.8 V0.26 V (0.04%)8.8 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.02%)689.9 V0.21 V (0.03%)7.1 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.01%)689.9 V0.16 V (0.02%)5.5 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.01%)689.9 V0.13 V (0.02%)4.4 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)689.9 V0.1 V (0.01%)3.3 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 32A over 20m at 690V (voltage drop: 5.93V or 0.86%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.