100 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 5 m (16.4 ft).
Copper Cable (≤3% Drop)25 mm²Drop: 0.74V (0.11%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.61V (0.09%)
Voltage at Load689.3 VLine Loss: 128.4 W
Max Power & Breaker119.51 kW100A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 12.36 V (1.79%) | 677.6 V | 20.38 V (2.95%) | 2140.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 7.41 V (1.07%) | 682.6 V | 12.23 V (1.77%) | 1284.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 4.63 V (0.67%) | 685.4 V | 7.64 V (1.11%) | 802.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 3.09 V (0.45%) | 686.9 V | 5.1 V (0.74%) | 535.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 1.85 V (0.27%) | 688.1 V | 3.06 V (0.44%) | 321.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 1.16 V (0.17%) | 688.8 V | 1.91 V (0.28%) | 200.6 W | Drop High |
| 25 mm² | 101 A | 78 A | 0.74 V (0.11%) | 689.3 V | 1.22 V (0.18%) | 128.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.53 V (0.08%) | 689.5 V | 0.87 V (0.13%) | 91.7 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.37 V (0.05%) | 689.6 V | 0.61 V (0.09%) | 64.2 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.26 V (0.04%) | 689.7 V | 0.44 V (0.06%) | 45.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.2 V (0.03%) | 689.8 V | 0.32 V (0.05%) | 33.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.15 V (0.02%) | 689.8 V | 0.25 V (0.04%) | 26.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.12 V (0.02%) | 689.9 V | 0.2 V (0.03%) | 21.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.1 V (0.01%) | 689.9 V | 0.17 V (0.02%) | 17.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.08 V (0.01%) | 689.9 V | 0.13 V (0.02%) | 13.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.06 V (0.01%) | 689.9 V | 0.1 V (0.01%) | 10.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.05 V (0.01%) | 690.0 V | 0.08 V (0.01%) | 8.0 W | ✓ OK (≤3%) |
FAQ — 100 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 100A at 5 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 100A over 5m at 690V (voltage drop: 0.74V or 0.11%).
What is the power capacity of 100A at 690V?
At unity power factor, 100A at 690V supports 119.51 kW with a standard 100A circuit breaker.
Related Lengths & Currents (690V)
100A · 10m (690V)100A · 15m (690V)100A · 20m (690V)100A · 25m (690V)100A · 30m (690V)100A · 35m (690V)100A · 40m (690V)100A · 45m (690V)100A · 50m (690V)100A · 60m (690V)100A · 70m (690V)10A · 5m (690V)16A · 5m (690V)20A · 5m (690V)25A · 5m (690V)32A · 5m (690V)40A · 5m (690V)50A · 5m (690V)63A · 5m (690V)80A · 5m (690V)125A · 5m (690V)160A · 5m (690V)200A · 5m (690V)