1000 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.56V (0.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.34V (2.66%)
Voltage at Load684.4 VLine Loss: 9630.0 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2965.27 V (429.75%)0.0 V4891.31 V (708.89%)5136000.0 WDrop High
2.5 mm²24 A18 A1779.16 V (257.85%)0.0 V2934.79 V (425.33%)3081600.0 WDrop High
4 mm²32 A25 A1111.98 V (161.16%)0.0 V1834.24 V (265.83%)1926000.0 WDrop High
6 mm²41 A32 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)1284000.0 WDrop High
10 mm²57 A44 A444.79 V (64.46%)245.2 V733.7 V (106.33%)770400.0 WDrop High
16 mm²76 A59 A277.99 V (40.29%)412.0 V458.56 V (66.46%)481500.0 WDrop High
25 mm²101 A78 A177.92 V (25.78%)512.1 V293.48 V (42.53%)308160.0 WDrop High
35 mm²125 A97 A127.08 V (18.42%)562.9 V209.63 V (30.38%)220114.3 WDrop High
50 mm²151 A118 A88.96 V (12.89%)601.0 V146.74 V (21.27%)154080.0 WDrop High
70 mm²192 A150 A63.54 V (9.21%)626.5 V104.81 V (15.19%)110057.1 WDrop High
95 mm²232 A181 A46.82 V (6.79%)643.2 V77.23 V (11.19%)81094.7 WDrop High
120 mm²269 A210 A37.07 V (5.37%)652.9 V61.14 V (8.86%)64200.0 WDrop High
150 mm²309 A241 A29.65 V (4.3%)660.3 V48.91 V (7.09%)51360.0 WDrop High
185 mm²353 A275 A24.04 V (3.48%)666.0 V39.66 V (5.75%)41643.2 WDrop High
240 mm²415 A324 A18.53 V (2.69%)671.5 V30.57 V (4.43%)32100.0 WDrop High
300 mm²477 A372 A14.83 V (2.15%)675.2 V24.46 V (3.54%)25680.0 WDrop High
400 mm²570 A445 A11.12 V (1.61%)678.9 V18.34 V (2.66%)19260.0 WDrop High

FAQ — 1000 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 120m at 690V (voltage drop: 5.56V or 0.81%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.