⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

1000 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)14× 400 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 30.89V (64.35%)
Voltage at Load46.7 VLine Loss: 1337.5 W
Max Power & Breaker48.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4993.33 V (10402.78%)0.0 V8236.67 V (17159.72%)4993333.3 WDrop High
2.5 mm²24 A18 A2996.0 V (6241.67%)0.0 V4942.0 V (10295.83%)2996000.0 WDrop High
4 mm²32 A25 A1872.5 V (3901.04%)0.0 V3088.75 V (6434.9%)1872500.0 WDrop High
6 mm²41 A32 A1248.33 V (2600.69%)0.0 V2059.17 V (4289.93%)1248333.3 WDrop High
10 mm²57 A44 A749.0 V (1560.42%)0.0 V1235.5 V (2573.96%)749000.0 WDrop High
16 mm²76 A59 A468.12 V (975.26%)0.0 V772.19 V (1608.72%)468125.0 WDrop High
25 mm²101 A78 A299.6 V (624.17%)0.0 V494.2 V (1029.58%)299600.0 WDrop High
35 mm²125 A97 A214.0 V (445.83%)0.0 V353.0 V (735.42%)214000.0 WDrop High
50 mm²151 A118 A149.8 V (312.08%)0.0 V247.1 V (514.79%)149800.0 WDrop High
70 mm²192 A150 A107.0 V (222.92%)0.0 V176.5 V (367.71%)107000.0 WDrop High
95 mm²232 A181 A78.84 V (164.25%)0.0 V130.05 V (270.94%)78842.1 WDrop High
120 mm²269 A210 A62.42 V (130.03%)0.0 V102.96 V (214.5%)62416.7 WDrop High
150 mm²309 A241 A49.93 V (104.03%)0.0 V82.37 V (171.6%)49933.3 WDrop High
185 mm²353 A275 A40.49 V (84.35%)7.5 V66.78 V (139.13%)40486.5 WDrop High
240 mm²415 A324 A31.21 V (65.02%)16.8 V51.48 V (107.25%)31208.3 WDrop High
300 mm²477 A372 A24.97 V (52.01%)23.0 V41.18 V (85.8%)24966.7 WDrop High
400 mm²570 A445 A18.72 V (39.01%)29.3 V30.89 V (64.35%)18725.0 WDrop High

FAQ — 1000 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 1000A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 14× 400 mm² copper cable for 1000A over 175m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 1000A at 48V?

At unity power factor, 1000A at 48V supports 48.0 kW with a standard 1000A circuit breaker.