1000 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 70 m (229.7 ft).
Copper Cable (≤3% Drop)6× 400 mm²Drop: 1.25V (2.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.36V (25.74%)
Voltage at Load46.8 VLine Loss: 1248.3 W
Max Power & Breaker48.0 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1997.33 V (4161.11%) | 0.0 V | 3294.67 V (6863.89%) | 1997333.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1198.4 V (2496.67%) | 0.0 V | 1976.8 V (4118.33%) | 1198400.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 749.0 V (1560.42%) | 0.0 V | 1235.5 V (2573.96%) | 749000.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 499.33 V (1040.28%) | 0.0 V | 823.67 V (1715.97%) | 499333.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 299.6 V (624.17%) | 0.0 V | 494.2 V (1029.58%) | 299600.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 187.25 V (390.1%) | 0.0 V | 308.88 V (643.49%) | 187250.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 119.84 V (249.67%) | 0.0 V | 197.68 V (411.83%) | 119840.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 85.6 V (178.33%) | 0.0 V | 141.2 V (294.17%) | 85600.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 59.92 V (124.83%) | 0.0 V | 98.84 V (205.92%) | 59920.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 42.8 V (89.17%) | 5.2 V | 70.6 V (147.08%) | 42800.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 31.54 V (65.7%) | 16.5 V | 52.02 V (108.38%) | 31536.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 24.97 V (52.01%) | 23.0 V | 41.18 V (85.8%) | 24966.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 19.97 V (41.61%) | 28.0 V | 32.95 V (68.64%) | 19973.3 W | Drop High |
| 185 mm² | 353 A | 275 A | 16.19 V (33.74%) | 31.8 V | 26.71 V (55.65%) | 16194.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 12.48 V (26.01%) | 35.5 V | 20.59 V (42.9%) | 12483.3 W | Drop High |
| 300 mm² | 477 A | 372 A | 9.99 V (20.81%) | 38.0 V | 16.47 V (34.32%) | 9986.7 W | Drop High |
| 400 mm² | 570 A | 445 A | 7.49 V (15.6%) | 40.5 V | 12.36 V (25.74%) | 7490.0 W | Drop High |
FAQ — 1000 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
What mm² cable size is required for 1000A at 70 meters (48V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6× 400 mm² copper cable for 1000A over 70m at 48V (voltage drop: 1.25V or 2.6%).
What is the power capacity of 1000A at 48V?
At unity power factor, 1000A at 48V supports 48.0 kW with a standard 1000A circuit breaker.
Related Lengths & Currents (48V)
1000A · 5m (48V)1000A · 10m (48V)1000A · 15m (48V)1000A · 20m (48V)1000A · 25m (48V)1000A · 30m (48V)1000A · 35m (48V)1000A · 40m (48V)1000A · 45m (48V)1000A · 50m (48V)1000A · 60m (48V)10A · 70m (48V)16A · 70m (48V)20A · 70m (48V)25A · 70m (48V)32A · 70m (48V)40A · 70m (48V)50A · 70m (48V)63A · 70m (48V)80A · 70m (48V)100A · 70m (48V)125A · 70m (48V)160A · 70m (48V)200A · 70m (48V)