125 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.3V (2.71%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.32V (2.76%)
Voltage at Load46.7 VLine Loss: 162.7 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A160.5 V (334.38%)0.0 V264.75 V (551.56%)20062.5 WDrop High
2.5 mm²24 A18 A96.3 V (200.62%)0.0 V158.85 V (330.94%)12037.5 WDrop High
4 mm²32 A25 A60.19 V (125.39%)0.0 V99.28 V (206.84%)7523.4 WDrop High
6 mm²41 A32 A40.12 V (83.59%)7.9 V66.19 V (137.89%)5015.6 WDrop High
10 mm²57 A44 A24.07 V (50.16%)23.9 V39.71 V (82.73%)3009.4 WDrop High
16 mm²76 A59 A15.05 V (31.35%)33.0 V24.82 V (51.71%)1880.9 WDrop High
25 mm²101 A78 A9.63 V (20.06%)38.4 V15.88 V (33.09%)1203.8 WDrop High
35 mm²125 A97 A6.88 V (14.33%)41.1 V11.35 V (23.64%)859.8 WDrop High
50 mm²151 A118 A4.81 V (10.03%)43.2 V7.94 V (16.55%)601.9 WDrop High
70 mm²192 A150 A3.44 V (7.17%)44.6 V5.67 V (11.82%)429.9 WDrop High
95 mm²232 A181 A2.53 V (5.28%)45.5 V4.18 V (8.71%)316.8 WDrop High
120 mm²269 A210 A2.01 V (4.18%)46.0 V3.31 V (6.89%)250.8 W~ ≤5%
150 mm²309 A241 A1.6 V (3.34%)46.4 V2.65 V (5.52%)200.6 W~ ≤5%
185 mm²353 A275 A1.3 V (2.71%)46.7 V2.15 V (4.47%)162.7 W✓ OK (≤3%)
240 mm²415 A324 A1.0 V (2.09%)47.0 V1.65 V (3.45%)125.4 W✓ OK (≤3%)
300 mm²477 A372 A0.8 V (1.67%)47.2 V1.32 V (2.76%)100.3 W✓ OK (≤3%)
400 mm²570 A445 A0.6 V (1.25%)47.4 V0.99 V (2.07%)75.2 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 45 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 125A over 45m at 48V (voltage drop: 1.3V or 2.71%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.