125 Amp Cable Size at 35 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 4.41V (1.92%)
Voltage at Load224.7 VLine Loss: 668.8 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.83 V (54.28%)105.2 V205.92 V (89.53%)15604.2 WDrop High
2.5 mm²24 A18 A74.9 V (32.57%)155.1 V123.55 V (53.72%)9362.5 WDrop High
4 mm²32 A25 A46.81 V (20.35%)183.2 V77.22 V (33.57%)5851.6 WDrop High
6 mm²41 A32 A31.21 V (13.57%)198.8 V51.48 V (22.38%)3901.0 WDrop High
10 mm²57 A44 A18.72 V (8.14%)211.3 V30.89 V (13.43%)2340.6 WDrop High
16 mm²76 A59 A11.7 V (5.09%)218.3 V19.3 V (8.39%)1462.9 WDrop High
25 mm²101 A78 A7.49 V (3.26%)222.5 V12.36 V (5.37%)936.2 WDrop High
35 mm²125 A97 A5.35 V (2.33%)224.7 V8.82 V (3.84%)668.8 W✓ OK (≤3%)
50 mm²151 A118 A3.75 V (1.63%)226.3 V6.18 V (2.69%)468.1 W✓ OK (≤3%)
70 mm²192 A150 A2.67 V (1.16%)227.3 V4.41 V (1.92%)334.4 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.86%)228.0 V3.25 V (1.41%)246.4 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.68%)228.4 V2.57 V (1.12%)195.1 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.54%)228.8 V2.06 V (0.9%)156.0 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.44%)229.0 V1.67 V (0.73%)126.5 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.34%)229.2 V1.29 V (0.56%)97.5 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.27%)229.4 V1.03 V (0.45%)78.0 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.2%)229.5 V0.77 V (0.34%)58.5 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 35 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 125A at 35 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 35m at 230V (voltage drop: 5.35V or 2.33%).

What is the power capacity of 125A at 230V?

At unity power factor, 125A at 230V supports 28.75 kW with a standard 125A circuit breaker.