16 Amp Cable Size at 35 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 35 m (114.8 ft).
Copper Cable (≤3% Drop)4 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 6.59V (2.86%)
Voltage at Load224.0 VLine Loss: 95.9 W
Max Power & Breaker3.68 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 15.98 V (6.95%) | 214.0 V | 26.36 V (11.46%) | 255.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 9.59 V (4.17%) | 220.4 V | 15.81 V (6.88%) | 153.4 W | ~ ≤5% |
| 4 mm² | 32 A | 25 A | 5.99 V (2.61%) | 224.0 V | 9.88 V (4.3%) | 95.9 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 3.99 V (1.74%) | 226.0 V | 6.59 V (2.86%) | 63.9 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.4 V (1.04%) | 227.6 V | 3.95 V (1.72%) | 38.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.5 V (0.65%) | 228.5 V | 2.47 V (1.07%) | 24.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.96 V (0.42%) | 229.0 V | 1.58 V (0.69%) | 15.3 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.68 V (0.3%) | 229.3 V | 1.13 V (0.49%) | 11.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.48 V (0.21%) | 229.5 V | 0.79 V (0.34%) | 7.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.34 V (0.15%) | 229.7 V | 0.56 V (0.25%) | 5.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.25 V (0.11%) | 229.7 V | 0.42 V (0.18%) | 4.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.2 V (0.09%) | 229.8 V | 0.33 V (0.14%) | 3.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.16 V (0.07%) | 229.8 V | 0.26 V (0.11%) | 2.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.13 V (0.06%) | 229.9 V | 0.21 V (0.09%) | 2.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.1 V (0.04%) | 229.9 V | 0.16 V (0.07%) | 1.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.08 V (0.03%) | 229.9 V | 0.13 V (0.06%) | 1.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.03%) | 229.9 V | 0.1 V (0.04%) | 1.0 W | ✓ OK (≤3%) |
FAQ — 16 Amp Cable Size at 35 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 16A at 35 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 16A over 35m at 230V (voltage drop: 5.99V or 2.61%).
What is the power capacity of 16A at 230V?
At unity power factor, 16A at 230V supports 3.68 kW with a standard 16A circuit breaker.
Related Lengths & Currents (230V)
16A · 5m (230V)16A · 10m (230V)16A · 15m (230V)16A · 20m (230V)16A · 25m (230V)16A · 30m (230V)16A · 40m (230V)16A · 45m (230V)16A · 50m (230V)16A · 60m (230V)16A · 70m (230V)10A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)