15 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 12.97V (1.88%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 12.84V (1.86%)
Voltage at Load677.0 VLine Loss: 337.1 W
Max Power & Breaker17.93 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.97 V (1.88%)677.0 V21.4 V (3.1%)337.1 W✓ OK (≤3%)
2.5 mm²24 A18 A7.78 V (1.13%)682.2 V12.84 V (1.86%)202.2 W✓ OK (≤3%)
4 mm²32 A25 A4.86 V (0.71%)685.1 V8.02 V (1.16%)126.4 W✓ OK (≤3%)
6 mm²41 A32 A3.24 V (0.47%)686.8 V5.35 V (0.78%)84.3 W✓ OK (≤3%)
10 mm²57 A44 A1.95 V (0.28%)688.1 V3.21 V (0.47%)50.6 W✓ OK (≤3%)
16 mm²76 A59 A1.22 V (0.18%)688.8 V2.01 V (0.29%)31.6 W✓ OK (≤3%)
25 mm²101 A78 A0.78 V (0.11%)689.2 V1.28 V (0.19%)20.2 W✓ OK (≤3%)
35 mm²125 A97 A0.56 V (0.08%)689.4 V0.92 V (0.13%)14.4 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.06%)689.6 V0.64 V (0.09%)10.1 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.04%)689.7 V0.46 V (0.07%)7.2 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.03%)689.8 V0.34 V (0.05%)5.3 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.02%)689.8 V0.27 V (0.04%)4.2 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.02%)689.9 V0.21 V (0.03%)3.4 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.02%)689.9 V0.17 V (0.03%)2.7 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.01%)689.9 V0.13 V (0.02%)2.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)689.9 V0.11 V (0.02%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)690.0 V0.08 V (0.01%)1.3 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 15A at 35 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 35m at 690V (voltage drop: 12.97V or 1.88%).

What is the power capacity of 15A at 690V?

At unity power factor, 15A at 690V supports 17.93 kW with a standard 15A circuit breaker.