15 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 16.68V (2.42%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 16.51V (2.39%)
Voltage at Load673.3 VLine Loss: 433.4 W
Max Power & Breaker17.93 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A16.68 V (2.42%)673.3 V27.51 V (3.99%)433.4 W✓ OK (≤3%)
2.5 mm²24 A18 A10.01 V (1.45%)680.0 V16.51 V (2.39%)260.0 W✓ OK (≤3%)
4 mm²32 A25 A6.25 V (0.91%)683.7 V10.32 V (1.5%)162.5 W✓ OK (≤3%)
6 mm²41 A32 A4.17 V (0.6%)685.8 V6.88 V (1.0%)108.3 W✓ OK (≤3%)
10 mm²57 A44 A2.5 V (0.36%)687.5 V4.13 V (0.6%)65.0 W✓ OK (≤3%)
16 mm²76 A59 A1.56 V (0.23%)688.4 V2.58 V (0.37%)40.6 W✓ OK (≤3%)
25 mm²101 A78 A1.0 V (0.15%)689.0 V1.65 V (0.24%)26.0 W✓ OK (≤3%)
35 mm²125 A97 A0.71 V (0.1%)689.3 V1.18 V (0.17%)18.6 W✓ OK (≤3%)
50 mm²151 A118 A0.5 V (0.07%)689.5 V0.83 V (0.12%)13.0 W✓ OK (≤3%)
70 mm²192 A150 A0.36 V (0.05%)689.6 V0.59 V (0.09%)9.3 W✓ OK (≤3%)
95 mm²232 A181 A0.26 V (0.04%)689.7 V0.43 V (0.06%)6.8 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.03%)689.8 V0.34 V (0.05%)5.4 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.02%)689.8 V0.28 V (0.04%)4.3 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.02%)689.9 V0.22 V (0.03%)3.5 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.02%)689.9 V0.17 V (0.02%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.01%)689.9 V0.14 V (0.02%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)689.9 V0.1 V (0.01%)1.6 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 15A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 45m at 690V (voltage drop: 16.68V or 2.42%).

What is the power capacity of 15A at 690V?

At unity power factor, 15A at 690V supports 17.93 kW with a standard 15A circuit breaker.