15 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 1.85V (0.27%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 1.83V (0.27%)
Voltage at Load688.1 VLine Loss: 48.1 W
Max Power & Breaker17.93 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1.85 V (0.27%)688.1 V3.06 V (0.44%)48.1 W✓ OK (≤3%)
2.5 mm²24 A18 A1.11 V (0.16%)688.9 V1.83 V (0.27%)28.9 W✓ OK (≤3%)
4 mm²32 A25 A0.69 V (0.1%)689.3 V1.15 V (0.17%)18.1 W✓ OK (≤3%)
6 mm²41 A32 A0.46 V (0.07%)689.5 V0.76 V (0.11%)12.0 W✓ OK (≤3%)
10 mm²57 A44 A0.28 V (0.04%)689.7 V0.46 V (0.07%)7.2 W✓ OK (≤3%)
16 mm²76 A59 A0.17 V (0.03%)689.8 V0.29 V (0.04%)4.5 W✓ OK (≤3%)
25 mm²101 A78 A0.11 V (0.02%)689.9 V0.18 V (0.03%)2.9 W✓ OK (≤3%)
35 mm²125 A97 A0.08 V (0.01%)689.9 V0.13 V (0.02%)2.1 W✓ OK (≤3%)
50 mm²151 A118 A0.06 V (0.01%)689.9 V0.09 V (0.01%)1.4 W✓ OK (≤3%)
70 mm²192 A150 A0.04 V (0.01%)690.0 V0.07 V (0.01%)1.0 W✓ OK (≤3%)
95 mm²232 A181 A0.03 V (0.0%)690.0 V0.05 V (0.01%)0.8 W✓ OK (≤3%)
120 mm²269 A210 A0.02 V (0.0%)690.0 V0.04 V (0.01%)0.6 W✓ OK (≤3%)
150 mm²309 A241 A0.02 V (0.0%)690.0 V0.03 V (0.0%)0.5 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.0%)690.0 V0.02 V (0.0%)0.4 W✓ OK (≤3%)
240 mm²415 A324 A0.01 V (0.0%)690.0 V0.02 V (0.0%)0.3 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.0%)690.0 V0.02 V (0.0%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)690.0 V0.01 V (0.0%)0.2 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 15A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 5m at 690V (voltage drop: 1.85V or 0.27%).

What is the power capacity of 15A at 690V?

At unity power factor, 15A at 690V supports 17.93 kW with a standard 15A circuit breaker.