15 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 20 m (65.6 ft).
Copper Cable (≤3% Drop)1.5 mm²Drop: 7.41V (1.07%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 7.34V (1.06%)
Voltage at Load682.6 VLine Loss: 192.6 W
Max Power & Breaker17.93 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 20m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 7.41 V (1.07%) | 682.6 V | 12.23 V (1.77%) | 192.6 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 4.45 V (0.64%) | 685.6 V | 7.34 V (1.06%) | 115.6 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 2.78 V (0.4%) | 687.2 V | 4.59 V (0.66%) | 72.2 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 1.85 V (0.27%) | 688.1 V | 3.06 V (0.44%) | 48.1 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.11 V (0.16%) | 688.9 V | 1.83 V (0.27%) | 28.9 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.69 V (0.1%) | 689.3 V | 1.15 V (0.17%) | 18.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.44 V (0.06%) | 689.6 V | 0.73 V (0.11%) | 11.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.32 V (0.05%) | 689.7 V | 0.52 V (0.08%) | 8.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.22 V (0.03%) | 689.8 V | 0.37 V (0.05%) | 5.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.16 V (0.02%) | 689.8 V | 0.26 V (0.04%) | 4.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.12 V (0.02%) | 689.9 V | 0.19 V (0.03%) | 3.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.09 V (0.01%) | 689.9 V | 0.15 V (0.02%) | 2.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.07 V (0.01%) | 689.9 V | 0.12 V (0.02%) | 1.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.06 V (0.01%) | 689.9 V | 0.1 V (0.01%) | 1.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.05 V (0.01%) | 690.0 V | 0.08 V (0.01%) | 1.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.04 V (0.01%) | 690.0 V | 0.06 V (0.01%) | 1.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.0%) | 690.0 V | 0.05 V (0.01%) | 0.7 W | ✓ OK (≤3%) |
FAQ — 15 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 15A at 20 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 20m at 690V (voltage drop: 7.41V or 1.07%).
What is the power capacity of 15A at 690V?
At unity power factor, 15A at 690V supports 17.93 kW with a standard 15A circuit breaker.
Related Lengths & Currents (690V)
15A · 5m (690V)15A · 10m (690V)15A · 15m (690V)15A · 25m (690V)15A · 30m (690V)15A · 35m (690V)15A · 40m (690V)15A · 45m (690V)15A · 50m (690V)15A · 60m (690V)15A · 70m (690V)10A · 20m (690V)16A · 20m (690V)20A · 20m (690V)25A · 20m (690V)32A · 20m (690V)40A · 20m (690V)50A · 20m (690V)63A · 20m (690V)80A · 20m (690V)100A · 20m (690V)125A · 20m (690V)160A · 20m (690V)200A · 20m (690V)