15 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 1.28V (2.67%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.06V (2.21%)
Voltage at Load46.7 VLine Loss: 19.3 W
Max Power & Breaker0.72 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.4 V (44.58%)26.6 V35.3 V (73.54%)321.0 WDrop High
2.5 mm²24 A18 A12.84 V (26.75%)35.2 V21.18 V (44.12%)192.6 WDrop High
4 mm²32 A25 A8.02 V (16.72%)40.0 V13.24 V (27.58%)120.4 WDrop High
6 mm²41 A32 A5.35 V (11.15%)42.6 V8.82 V (18.39%)80.2 WDrop High
10 mm²57 A44 A3.21 V (6.69%)44.8 V5.29 V (11.03%)48.1 WDrop High
16 mm²76 A59 A2.01 V (4.18%)46.0 V3.31 V (6.89%)30.1 W~ ≤5%
25 mm²101 A78 A1.28 V (2.67%)46.7 V2.12 V (4.41%)19.3 W✓ OK (≤3%)
35 mm²125 A97 A0.92 V (1.91%)47.1 V1.51 V (3.15%)13.8 W✓ OK (≤3%)
50 mm²151 A118 A0.64 V (1.34%)47.4 V1.06 V (2.21%)9.6 W✓ OK (≤3%)
70 mm²192 A150 A0.46 V (0.96%)47.5 V0.76 V (1.58%)6.9 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (0.7%)47.7 V0.56 V (1.16%)5.1 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (0.56%)47.7 V0.44 V (0.92%)4.0 W✓ OK (≤3%)
150 mm²309 A241 A0.21 V (0.45%)47.8 V0.35 V (0.74%)3.2 W✓ OK (≤3%)
185 mm²353 A275 A0.17 V (0.36%)47.8 V0.29 V (0.6%)2.6 W✓ OK (≤3%)
240 mm²415 A324 A0.13 V (0.28%)47.9 V0.22 V (0.46%)2.0 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.22%)47.9 V0.18 V (0.37%)1.6 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.17%)47.9 V0.13 V (0.28%)1.2 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 15A at 50 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 15A over 50m at 48V (voltage drop: 1.28V or 2.67%).

What is the power capacity of 15A at 48V?

At unity power factor, 15A at 48V supports 0.72 kW with a standard 15A circuit breaker.