15 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 1.4V (2.93%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 1.06V (2.21%)
Voltage at Load46.6 VLine Loss: 21.1 W
Max Power & Breaker0.72 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.98 V (31.21%)33.0 V24.71 V (51.48%)224.7 WDrop High
2.5 mm²24 A18 A8.99 V (18.73%)39.0 V14.83 V (30.89%)134.8 WDrop High
4 mm²32 A25 A5.62 V (11.7%)42.4 V9.27 V (19.3%)84.3 WDrop High
6 mm²41 A32 A3.75 V (7.8%)44.3 V6.18 V (12.87%)56.2 WDrop High
10 mm²57 A44 A2.25 V (4.68%)45.8 V3.71 V (7.72%)33.7 W~ ≤5%
16 mm²76 A59 A1.4 V (2.93%)46.6 V2.32 V (4.83%)21.1 W✓ OK (≤3%)
25 mm²101 A78 A0.9 V (1.87%)47.1 V1.48 V (3.09%)13.5 W✓ OK (≤3%)
35 mm²125 A97 A0.64 V (1.34%)47.4 V1.06 V (2.21%)9.6 W✓ OK (≤3%)
50 mm²151 A118 A0.45 V (0.94%)47.6 V0.74 V (1.54%)6.7 W✓ OK (≤3%)
70 mm²192 A150 A0.32 V (0.67%)47.7 V0.53 V (1.1%)4.8 W✓ OK (≤3%)
95 mm²232 A181 A0.24 V (0.49%)47.8 V0.39 V (0.81%)3.5 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.39%)47.8 V0.31 V (0.64%)2.8 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.31%)47.9 V0.25 V (0.51%)2.2 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.25%)47.9 V0.2 V (0.42%)1.8 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.2%)47.9 V0.15 V (0.32%)1.4 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.16%)47.9 V0.12 V (0.26%)1.1 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.12%)47.9 V0.09 V (0.19%)0.8 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 15A at 35 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 15A over 35m at 48V (voltage drop: 1.4V or 2.93%).

What is the power capacity of 15A at 48V?

At unity power factor, 15A at 48V supports 0.72 kW with a standard 15A circuit breaker.