⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

15 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 1.16V (2.41%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 1.36V (2.84%)
Voltage at Load46.8 VLine Loss: 17.3 W
Max Power & Breaker0.72 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.26 V (40.13%)28.7 V31.77 V (66.19%)288.9 WDrop High
2.5 mm²24 A18 A11.56 V (24.07%)36.4 V19.06 V (39.71%)173.3 WDrop High
4 mm²32 A25 A7.22 V (15.05%)40.8 V11.91 V (24.82%)108.3 WDrop High
6 mm²41 A32 A4.82 V (10.03%)43.2 V7.94 V (16.55%)72.2 WDrop High
10 mm²57 A44 A2.89 V (6.02%)45.1 V4.77 V (9.93%)43.3 WDrop High
16 mm²76 A59 A1.81 V (3.76%)46.2 V2.98 V (6.21%)27.1 W~ ≤5%
25 mm²101 A78 A1.16 V (2.41%)46.8 V1.91 V (3.97%)17.3 W✓ OK (≤3%)
35 mm²125 A97 A0.83 V (1.72%)47.2 V1.36 V (2.84%)12.4 W✓ OK (≤3%)
50 mm²151 A118 A0.58 V (1.2%)47.4 V0.95 V (1.99%)8.7 W✓ OK (≤3%)
70 mm²192 A150 A0.41 V (0.86%)47.6 V0.68 V (1.42%)6.2 W✓ OK (≤3%)
95 mm²232 A181 A0.3 V (0.63%)47.7 V0.5 V (1.05%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.24 V (0.5%)47.8 V0.4 V (0.83%)3.6 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.4%)47.8 V0.32 V (0.66%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.33%)47.8 V0.26 V (0.54%)2.3 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.25%)47.9 V0.2 V (0.41%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.2%)47.9 V0.16 V (0.33%)1.4 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.15%)47.9 V0.12 V (0.25%)1.1 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 15A at 45 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 15A over 45m at 48V (voltage drop: 1.16V or 2.41%).

What is the power capacity of 15A at 48V?

At unity power factor, 15A at 48V supports 0.72 kW with a standard 15A circuit breaker.