16 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.68V (2.82%)
Voltage at Load23.4 VLine Loss: 10.3 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.85 V (28.53%)17.2 V11.3 V (47.07%)109.6 WDrop High
2.5 mm²24 A18 A4.11 V (17.12%)19.9 V6.78 V (28.24%)65.7 WDrop High
4 mm²32 A25 A2.57 V (10.7%)21.4 V4.24 V (17.65%)41.1 WDrop High
6 mm²41 A32 A1.71 V (7.13%)22.3 V2.82 V (11.77%)27.4 WDrop High
10 mm²57 A44 A1.03 V (4.28%)23.0 V1.69 V (7.06%)16.4 W~ ≤5%
16 mm²76 A59 A0.64 V (2.67%)23.4 V1.06 V (4.41%)10.3 W✓ OK (≤3%)
25 mm²101 A78 A0.41 V (1.71%)23.6 V0.68 V (2.82%)6.6 W✓ OK (≤3%)
35 mm²125 A97 A0.29 V (1.22%)23.7 V0.48 V (2.02%)4.7 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.86%)23.8 V0.34 V (1.41%)3.3 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.61%)23.9 V0.24 V (1.01%)2.3 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.45%)23.9 V0.18 V (0.74%)1.7 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.36%)23.9 V0.14 V (0.59%)1.4 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.29%)23.9 V0.11 V (0.47%)1.1 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.23%)23.9 V0.09 V (0.38%)0.9 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.18%)24.0 V0.07 V (0.29%)0.7 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.14%)24.0 V0.06 V (0.24%)0.5 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.11%)24.0 V0.04 V (0.18%)0.4 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 15 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 16A over 15m at 24V (voltage drop: 0.64V or 2.67%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.