25 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.53V (2.21%)
Voltage at Load23.4 VLine Loss: 16.1 W
Max Power & Breaker0.6 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A10.7 V (44.58%)13.3 V17.65 V (73.54%)267.5 WDrop High
2.5 mm²24 A18 A6.42 V (26.75%)17.6 V10.59 V (44.12%)160.5 WDrop High
4 mm²32 A25 A4.01 V (16.72%)20.0 V6.62 V (27.58%)100.3 WDrop High
6 mm²41 A32 A2.67 V (11.15%)21.3 V4.41 V (18.39%)66.9 WDrop High
10 mm²57 A44 A1.61 V (6.69%)22.4 V2.65 V (11.03%)40.1 WDrop High
16 mm²76 A59 A1.0 V (4.18%)23.0 V1.65 V (6.89%)25.1 W~ ≤5%
25 mm²101 A78 A0.64 V (2.67%)23.4 V1.06 V (4.41%)16.1 W✓ OK (≤3%)
35 mm²125 A97 A0.46 V (1.91%)23.5 V0.76 V (3.15%)11.5 W✓ OK (≤3%)
50 mm²151 A118 A0.32 V (1.34%)23.7 V0.53 V (2.21%)8.0 W✓ OK (≤3%)
70 mm²192 A150 A0.23 V (0.96%)23.8 V0.38 V (1.58%)5.7 W✓ OK (≤3%)
95 mm²232 A181 A0.17 V (0.7%)23.8 V0.28 V (1.16%)4.2 W✓ OK (≤3%)
120 mm²269 A210 A0.13 V (0.56%)23.9 V0.22 V (0.92%)3.3 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.45%)23.9 V0.18 V (0.74%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.36%)23.9 V0.14 V (0.6%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.28%)23.9 V0.11 V (0.46%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.22%)23.9 V0.09 V (0.37%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.17%)24.0 V0.07 V (0.28%)1.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 25A at 15 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 25A over 15m at 24V (voltage drop: 0.64V or 2.67%).

What is the power capacity of 25A at 24V?

At unity power factor, 25A at 24V supports 0.6 kW with a standard 25A circuit breaker.