150 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 0.56V (0.13%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.66V (0.16%)
Voltage at Load414.4 VLine Loss: 144.4 W
Max Power & Breaker107.82 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.53 V (4.47%)396.5 V30.57 V (7.37%)4815.0 WDrop High
2.5 mm²24 A18 A11.12 V (2.68%)403.9 V18.34 V (4.42%)2889.0 WDrop High
4 mm²32 A25 A6.95 V (1.67%)408.1 V11.46 V (2.76%)1805.6 WDrop High
6 mm²41 A32 A4.63 V (1.12%)410.4 V7.64 V (1.84%)1203.8 WDrop High
10 mm²57 A44 A2.78 V (0.67%)412.2 V4.59 V (1.1%)722.2 WDrop High
16 mm²76 A59 A1.74 V (0.42%)413.3 V2.87 V (0.69%)451.4 WDrop High
25 mm²101 A78 A1.11 V (0.27%)413.9 V1.83 V (0.44%)288.9 WDrop High
35 mm²125 A97 A0.79 V (0.19%)414.2 V1.31 V (0.32%)206.4 WDrop High
50 mm²151 A118 A0.56 V (0.13%)414.4 V0.92 V (0.22%)144.4 W✓ OK (≤3%)
70 mm²192 A150 A0.4 V (0.1%)414.6 V0.66 V (0.16%)103.2 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.07%)414.7 V0.48 V (0.12%)76.0 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.06%)414.8 V0.38 V (0.09%)60.2 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.04%)414.8 V0.31 V (0.07%)48.1 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.04%)414.8 V0.25 V (0.06%)39.0 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.03%)414.9 V0.19 V (0.05%)30.1 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)414.9 V0.15 V (0.04%)24.1 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)414.9 V0.11 V (0.03%)18.1 W✓ OK (≤3%)

FAQ — 150 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 150A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 150A over 5m at 415V (voltage drop: 0.56V or 0.13%).

What is the power capacity of 150A at 415V?

At unity power factor, 150A at 415V supports 107.82 kW with a standard 150A circuit breaker.