150 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 4.45V (1.07%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.24V (1.26%)
Voltage at Load410.6 VLine Loss: 1155.6 W
Max Power & Breaker107.82 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A148.26 V (35.73%)266.7 V244.57 V (58.93%)38520.0 WDrop High
2.5 mm²24 A18 A88.96 V (21.44%)326.0 V146.74 V (35.36%)23112.0 WDrop High
4 mm²32 A25 A55.6 V (13.4%)359.4 V91.71 V (22.1%)14445.0 WDrop High
6 mm²41 A32 A37.07 V (8.93%)377.9 V61.14 V (14.73%)9630.0 WDrop High
10 mm²57 A44 A22.24 V (5.36%)392.8 V36.68 V (8.84%)5778.0 WDrop High
16 mm²76 A59 A13.9 V (3.35%)401.1 V22.93 V (5.52%)3611.2 WDrop High
25 mm²101 A78 A8.9 V (2.14%)406.1 V14.67 V (3.54%)2311.2 WDrop High
35 mm²125 A97 A6.35 V (1.53%)408.6 V10.48 V (2.53%)1650.9 WDrop High
50 mm²151 A118 A4.45 V (1.07%)410.6 V7.34 V (1.77%)1155.6 W✓ OK (≤3%)
70 mm²192 A150 A3.18 V (0.77%)411.8 V5.24 V (1.26%)825.4 W✓ OK (≤3%)
95 mm²232 A181 A2.34 V (0.56%)412.7 V3.86 V (0.93%)608.2 W✓ OK (≤3%)
120 mm²269 A210 A1.85 V (0.45%)413.1 V3.06 V (0.74%)481.5 W✓ OK (≤3%)
150 mm²309 A241 A1.48 V (0.36%)413.5 V2.45 V (0.59%)385.2 W✓ OK (≤3%)
185 mm²353 A275 A1.2 V (0.29%)413.8 V1.98 V (0.48%)312.3 W✓ OK (≤3%)
240 mm²415 A324 A0.93 V (0.22%)414.1 V1.53 V (0.37%)240.8 W✓ OK (≤3%)
300 mm²477 A372 A0.74 V (0.18%)414.3 V1.22 V (0.29%)192.6 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.13%)414.4 V0.92 V (0.22%)144.4 W✓ OK (≤3%)

FAQ — 150 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 150A at 40 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 150A over 40m at 415V (voltage drop: 4.45V or 1.07%).

What is the power capacity of 150A at 415V?

At unity power factor, 150A at 415V supports 107.82 kW with a standard 150A circuit breaker.