150 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 2.78V (0.67%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 3.28V (0.79%)
Voltage at Load412.2 VLine Loss: 722.2 W
Max Power & Breaker107.82 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (22.33%)322.3 V152.85 V (36.83%)24075.0 WDrop High
2.5 mm²24 A18 A55.6 V (13.4%)359.4 V91.71 V (22.1%)14445.0 WDrop High
4 mm²32 A25 A34.75 V (8.37%)380.3 V57.32 V (13.81%)9028.1 WDrop High
6 mm²41 A32 A23.17 V (5.58%)391.8 V38.21 V (9.21%)6018.7 WDrop High
10 mm²57 A44 A13.9 V (3.35%)401.1 V22.93 V (5.52%)3611.2 WDrop High
16 mm²76 A59 A8.69 V (2.09%)406.3 V14.33 V (3.45%)2257.0 WDrop High
25 mm²101 A78 A5.56 V (1.34%)409.4 V9.17 V (2.21%)1444.5 WDrop High
35 mm²125 A97 A3.97 V (0.96%)411.0 V6.55 V (1.58%)1031.8 WDrop High
50 mm²151 A118 A2.78 V (0.67%)412.2 V4.59 V (1.1%)722.2 W✓ OK (≤3%)
70 mm²192 A150 A1.99 V (0.48%)413.0 V3.28 V (0.79%)515.9 W✓ OK (≤3%)
95 mm²232 A181 A1.46 V (0.35%)413.5 V2.41 V (0.58%)380.1 W✓ OK (≤3%)
120 mm²269 A210 A1.16 V (0.28%)413.8 V1.91 V (0.46%)300.9 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.22%)414.1 V1.53 V (0.37%)240.7 W✓ OK (≤3%)
185 mm²353 A275 A0.75 V (0.18%)414.2 V1.24 V (0.3%)195.2 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.14%)414.4 V0.96 V (0.23%)150.5 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.11%)414.5 V0.76 V (0.18%)120.4 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.08%)414.7 V0.57 V (0.14%)90.3 W✓ OK (≤3%)

FAQ — 150 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 150A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 150A over 25m at 415V (voltage drop: 2.78V or 0.67%).

What is the power capacity of 150A at 415V?

At unity power factor, 150A at 415V supports 107.82 kW with a standard 150A circuit breaker.