150 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 80 m (262.5 ft).
Copper Cable (≤3% Drop)400 mm²Drop: 1.28V (2.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.12V (4.41%)
Voltage at Load46.7 VLine Loss: 192.6 W
Max Power & Breaker7.2 kW150A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 342.4 V (713.33%) | 0.0 V | 564.8 V (1176.67%) | 51360.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 205.44 V (428.0%) | 0.0 V | 338.88 V (706.0%) | 30816.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 128.4 V (267.5%) | 0.0 V | 211.8 V (441.25%) | 19260.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 85.6 V (178.33%) | 0.0 V | 141.2 V (294.17%) | 12840.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 51.36 V (107.0%) | 0.0 V | 84.72 V (176.5%) | 7704.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 32.1 V (66.88%) | 15.9 V | 52.95 V (110.31%) | 4815.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 20.54 V (42.8%) | 27.5 V | 33.89 V (70.6%) | 3081.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 14.67 V (30.57%) | 33.3 V | 24.21 V (50.43%) | 2201.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 10.27 V (21.4%) | 37.7 V | 16.94 V (35.3%) | 1540.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 7.34 V (15.29%) | 40.7 V | 12.1 V (25.21%) | 1100.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 5.41 V (11.26%) | 42.6 V | 8.92 V (18.58%) | 810.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 4.28 V (8.92%) | 43.7 V | 7.06 V (14.71%) | 642.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 3.42 V (7.13%) | 44.6 V | 5.65 V (11.77%) | 513.6 W | Drop High |
| 185 mm² | 353 A | 275 A | 2.78 V (5.78%) | 45.2 V | 4.58 V (9.54%) | 416.4 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.14 V (4.46%) | 45.9 V | 3.53 V (7.35%) | 321.0 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 1.71 V (3.57%) | 46.3 V | 2.82 V (5.88%) | 256.8 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 1.28 V (2.67%) | 46.7 V | 2.12 V (4.41%) | 192.6 W | ✓ OK (≤3%) |
FAQ — 150 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
What mm² cable size is required for 150A at 80 meters (48V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 150A over 80m at 48V (voltage drop: 1.28V or 2.67%).
What is the power capacity of 150A at 48V?
At unity power factor, 150A at 48V supports 7.2 kW with a standard 150A circuit breaker.
Related Lengths & Currents (48V)
150A · 5m (48V)150A · 10m (48V)150A · 15m (48V)150A · 20m (48V)150A · 25m (48V)150A · 30m (48V)150A · 35m (48V)150A · 40m (48V)150A · 45m (48V)150A · 50m (48V)150A · 60m (48V)150A · 70m (48V)10A · 80m (48V)16A · 80m (48V)20A · 80m (48V)25A · 80m (48V)32A · 80m (48V)40A · 80m (48V)50A · 80m (48V)63A · 80m (48V)80A · 80m (48V)100A · 80m (48V)125A · 80m (48V)160A · 80m (48V)200A · 80m (48V)