125 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 1.99V (0.29%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.64V (0.24%)
Voltage at Load688.0 VLine Loss: 429.9 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A46.33 V (6.71%)643.7 V76.43 V (11.08%)10031.2 WDrop High
2.5 mm²24 A18 A27.8 V (4.03%)662.2 V45.86 V (6.65%)6018.8 WDrop High
4 mm²32 A25 A17.37 V (2.52%)672.6 V28.66 V (4.15%)3761.7 WDrop High
6 mm²41 A32 A11.58 V (1.68%)678.4 V19.11 V (2.77%)2507.8 WDrop High
10 mm²57 A44 A6.95 V (1.01%)683.1 V11.46 V (1.66%)1504.7 WDrop High
16 mm²76 A59 A4.34 V (0.63%)685.7 V7.17 V (1.04%)940.4 WDrop High
25 mm²101 A78 A2.78 V (0.4%)687.2 V4.59 V (0.66%)601.9 WDrop High
35 mm²125 A97 A1.99 V (0.29%)688.0 V3.28 V (0.47%)429.9 W✓ OK (≤3%)
50 mm²151 A118 A1.39 V (0.2%)688.6 V2.29 V (0.33%)300.9 W✓ OK (≤3%)
70 mm²192 A150 A0.99 V (0.14%)689.0 V1.64 V (0.24%)215.0 W✓ OK (≤3%)
95 mm²232 A181 A0.73 V (0.11%)689.3 V1.21 V (0.17%)158.4 W✓ OK (≤3%)
120 mm²269 A210 A0.58 V (0.08%)689.4 V0.96 V (0.14%)125.4 W✓ OK (≤3%)
150 mm²309 A241 A0.46 V (0.07%)689.5 V0.76 V (0.11%)100.3 W✓ OK (≤3%)
185 mm²353 A275 A0.38 V (0.05%)689.6 V0.62 V (0.09%)81.3 W✓ OK (≤3%)
240 mm²415 A324 A0.29 V (0.04%)689.7 V0.48 V (0.07%)62.7 W✓ OK (≤3%)
300 mm²477 A372 A0.23 V (0.03%)689.8 V0.38 V (0.06%)50.2 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.03%)689.8 V0.29 V (0.04%)37.6 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 15m at 690V (voltage drop: 1.99V or 0.29%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.