32 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 4.45V (0.64%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.89V (0.71%)
Voltage at Load685.6 VLine Loss: 246.5 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.86 V (1.72%)678.1 V19.57 V (2.84%)657.4 WDrop High
2.5 mm²24 A18 A7.12 V (1.03%)682.9 V11.74 V (1.7%)394.4 WDrop High
4 mm²32 A25 A4.45 V (0.64%)685.6 V7.34 V (1.06%)246.5 W✓ OK (≤3%)
6 mm²41 A32 A2.97 V (0.43%)687.0 V4.89 V (0.71%)164.4 W✓ OK (≤3%)
10 mm²57 A44 A1.78 V (0.26%)688.2 V2.93 V (0.43%)98.6 W✓ OK (≤3%)
16 mm²76 A59 A1.11 V (0.16%)688.9 V1.83 V (0.27%)61.6 W✓ OK (≤3%)
25 mm²101 A78 A0.71 V (0.1%)689.3 V1.17 V (0.17%)39.4 W✓ OK (≤3%)
35 mm²125 A97 A0.51 V (0.07%)689.5 V0.84 V (0.12%)28.2 W✓ OK (≤3%)
50 mm²151 A118 A0.36 V (0.05%)689.6 V0.59 V (0.09%)19.7 W✓ OK (≤3%)
70 mm²192 A150 A0.25 V (0.04%)689.7 V0.42 V (0.06%)14.1 W✓ OK (≤3%)
95 mm²232 A181 A0.19 V (0.03%)689.8 V0.31 V (0.04%)10.4 W✓ OK (≤3%)
120 mm²269 A210 A0.15 V (0.02%)689.9 V0.24 V (0.04%)8.2 W✓ OK (≤3%)
150 mm²309 A241 A0.12 V (0.02%)689.9 V0.2 V (0.03%)6.6 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.01%)689.9 V0.16 V (0.02%)5.3 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.01%)689.9 V0.12 V (0.02%)4.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)689.9 V0.1 V (0.01%)3.3 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)690.0 V0.07 V (0.01%)2.5 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 32A over 15m at 690V (voltage drop: 4.45V or 0.64%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.