20 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 4.45V (0.64%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 4.59V (0.66%)
Voltage at Load685.6 VLine Loss: 154.1 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.41 V (1.07%)682.6 V12.23 V (1.77%)256.8 WDrop High
2.5 mm²24 A18 A4.45 V (0.64%)685.6 V7.34 V (1.06%)154.1 W✓ OK (≤3%)
4 mm²32 A25 A2.78 V (0.4%)687.2 V4.59 V (0.66%)96.3 W✓ OK (≤3%)
6 mm²41 A32 A1.85 V (0.27%)688.1 V3.06 V (0.44%)64.2 W✓ OK (≤3%)
10 mm²57 A44 A1.11 V (0.16%)688.9 V1.83 V (0.27%)38.5 W✓ OK (≤3%)
16 mm²76 A59 A0.69 V (0.1%)689.3 V1.15 V (0.17%)24.1 W✓ OK (≤3%)
25 mm²101 A78 A0.44 V (0.06%)689.6 V0.73 V (0.11%)15.4 W✓ OK (≤3%)
35 mm²125 A97 A0.32 V (0.05%)689.7 V0.52 V (0.08%)11.0 W✓ OK (≤3%)
50 mm²151 A118 A0.22 V (0.03%)689.8 V0.37 V (0.05%)7.7 W✓ OK (≤3%)
70 mm²192 A150 A0.16 V (0.02%)689.8 V0.26 V (0.04%)5.5 W✓ OK (≤3%)
95 mm²232 A181 A0.12 V (0.02%)689.9 V0.19 V (0.03%)4.1 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.01%)689.9 V0.15 V (0.02%)3.2 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.01%)689.9 V0.12 V (0.02%)2.6 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.01%)689.9 V0.1 V (0.01%)2.1 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.01%)690.0 V0.08 V (0.01%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.01%)690.0 V0.06 V (0.01%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.0%)690.0 V0.05 V (0.01%)1.0 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 20A over 15m at 690V (voltage drop: 4.45V or 0.64%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.