175 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 11.26V (2.71%)
Voltage at Load405.7 VLine Loss: 2808.7 W
Max Power & Breaker125.79 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A432.44 V (104.2%)0.0 V713.32 V (171.88%)131075.0 WDrop High
2.5 mm²24 A18 A259.46 V (62.52%)155.5 V427.99 V (103.13%)78645.0 WDrop High
4 mm²32 A25 A162.16 V (39.08%)252.8 V267.49 V (64.46%)49153.1 WDrop High
6 mm²41 A32 A108.11 V (26.05%)306.9 V178.33 V (42.97%)32768.8 WDrop High
10 mm²57 A44 A64.87 V (15.63%)350.1 V107.0 V (25.78%)19661.2 WDrop High
16 mm²76 A59 A40.54 V (9.77%)374.5 V66.87 V (16.11%)12288.3 WDrop High
25 mm²101 A78 A25.95 V (6.25%)389.1 V42.8 V (10.31%)7864.5 WDrop High
35 mm²125 A97 A18.53 V (4.47%)396.5 V30.57 V (7.37%)5617.5 WDrop High
50 mm²151 A118 A12.97 V (3.13%)402.0 V21.4 V (5.16%)3932.2 WDrop High
70 mm²192 A150 A9.27 V (2.23%)405.7 V15.29 V (3.68%)2808.7 W✓ OK (≤3%)
95 mm²232 A181 A6.83 V (1.65%)408.2 V11.26 V (2.71%)2069.6 W✓ OK (≤3%)
120 mm²269 A210 A5.41 V (1.3%)409.6 V8.92 V (2.15%)1638.4 W✓ OK (≤3%)
150 mm²309 A241 A4.32 V (1.04%)410.7 V7.13 V (1.72%)1310.7 W✓ OK (≤3%)
185 mm²353 A275 A3.51 V (0.84%)411.5 V5.78 V (1.39%)1062.8 W✓ OK (≤3%)
240 mm²415 A324 A2.7 V (0.65%)412.3 V4.46 V (1.07%)819.2 W✓ OK (≤3%)
300 mm²477 A372 A2.16 V (0.52%)412.8 V3.57 V (0.86%)655.4 W✓ OK (≤3%)
400 mm²570 A445 A1.62 V (0.39%)413.4 V2.67 V (0.64%)491.5 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 175A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 175A over 100m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 175A at 415V?

At unity power factor, 175A at 415V supports 125.79 kW with a standard 175A circuit breaker.