175 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 11.95V (2.99%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.12V (2.53%)
Voltage at Load388.1 VLine Loss: 3621.8 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A756.76 V (189.19%)0.0 V1248.3 V (312.08%)229381.2 WDrop High
2.5 mm²24 A18 A454.06 V (113.51%)0.0 V748.98 V (187.25%)137628.7 WDrop High
4 mm²32 A25 A283.79 V (70.95%)116.2 V468.11 V (117.03%)86018.0 WDrop High
6 mm²41 A32 A189.19 V (47.3%)210.8 V312.08 V (78.02%)57345.3 WDrop High
10 mm²57 A44 A113.51 V (28.38%)286.5 V187.25 V (46.81%)34407.2 WDrop High
16 mm²76 A59 A70.95 V (17.74%)329.1 V117.03 V (29.26%)21504.5 WDrop High
25 mm²101 A78 A45.41 V (11.35%)354.6 V74.9 V (18.72%)13762.9 WDrop High
35 mm²125 A97 A32.43 V (8.11%)367.6 V53.5 V (13.37%)9830.6 WDrop High
50 mm²151 A118 A22.7 V (5.68%)377.3 V37.45 V (9.36%)6881.4 WDrop High
70 mm²192 A150 A16.22 V (4.05%)383.8 V26.75 V (6.69%)4915.3 W~ ≤5%
95 mm²232 A181 A11.95 V (2.99%)388.1 V19.71 V (4.93%)3621.8 W✓ OK (≤3%)
120 mm²269 A210 A9.46 V (2.36%)390.5 V15.6 V (3.9%)2867.3 W✓ OK (≤3%)
150 mm²309 A241 A7.57 V (1.89%)392.4 V12.48 V (3.12%)2293.8 W✓ OK (≤3%)
185 mm²353 A275 A6.14 V (1.53%)393.9 V10.12 V (2.53%)1859.8 W✓ OK (≤3%)
240 mm²415 A324 A4.73 V (1.18%)395.3 V7.8 V (1.95%)1433.6 W✓ OK (≤3%)
300 mm²477 A372 A3.78 V (0.95%)396.2 V6.24 V (1.56%)1146.9 W✓ OK (≤3%)
400 mm²570 A445 A2.84 V (0.71%)397.2 V4.68 V (1.17%)860.2 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 175A at 175 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 175A over 175m at 400V (voltage drop: 11.95V or 2.99%).

What is the power capacity of 175A at 400V?

At unity power factor, 175A at 400V supports 121.24 kW with a standard 175A circuit breaker.