175 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.09V (2.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.41V (11.26%)
Voltage at Load46.9 VLine Loss: 191.2 W
Max Power & Breaker8.4 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A873.83 V (1820.49%)0.0 V1441.42 V (3002.95%)152920.8 WDrop High
2.5 mm²24 A18 A524.3 V (1092.29%)0.0 V864.85 V (1801.77%)91752.5 WDrop High
4 mm²32 A25 A327.69 V (682.68%)0.0 V540.53 V (1126.11%)57345.3 WDrop High
6 mm²41 A32 A218.46 V (455.12%)0.0 V360.35 V (750.74%)38230.2 WDrop High
10 mm²57 A44 A131.07 V (273.07%)0.0 V216.21 V (450.44%)22938.1 WDrop High
16 mm²76 A59 A81.92 V (170.67%)0.0 V135.13 V (281.53%)14336.3 WDrop High
25 mm²101 A78 A52.43 V (109.23%)0.0 V86.48 V (180.18%)9175.2 WDrop High
35 mm²125 A97 A37.45 V (78.02%)10.6 V61.77 V (128.7%)6553.7 WDrop High
50 mm²151 A118 A26.21 V (54.61%)21.8 V43.24 V (90.09%)4587.6 WDrop High
70 mm²192 A150 A18.72 V (39.01%)29.3 V30.89 V (64.35%)3276.9 WDrop High
95 mm²232 A181 A13.8 V (28.74%)34.2 V22.76 V (47.42%)2414.5 WDrop High
120 mm²269 A210 A10.92 V (22.76%)37.1 V18.02 V (37.54%)1911.5 WDrop High
150 mm²309 A241 A8.74 V (18.2%)39.3 V14.41 V (30.03%)1529.2 WDrop High
185 mm²353 A275 A7.09 V (14.76%)40.9 V11.69 V (24.35%)1239.9 WDrop High
240 mm²415 A324 A5.46 V (11.38%)42.5 V9.01 V (18.77%)955.8 WDrop High
300 mm²477 A372 A4.37 V (9.1%)43.6 V7.21 V (15.01%)764.6 WDrop High
400 mm²570 A445 A3.28 V (6.83%)44.7 V5.41 V (11.26%)573.5 WDrop High

FAQ — 175 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 175A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 175A over 175m at 48V (voltage drop: 1.09V or 2.28%).

What is the power capacity of 175A at 48V?

At unity power factor, 175A at 48V supports 8.4 kW with a standard 175A circuit breaker.