⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

175 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 1.85V (0.27%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 2.25V (0.33%)
Voltage at Load688.1 VLine Loss: 561.8 W
Max Power & Breaker209.15 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A86.49 V (12.53%)603.5 V142.66 V (20.68%)26215.0 WDrop High
2.5 mm²24 A18 A51.89 V (7.52%)638.1 V85.6 V (12.41%)15729.0 WDrop High
4 mm²32 A25 A32.43 V (4.7%)657.6 V53.5 V (7.75%)9830.6 WDrop High
6 mm²41 A32 A21.62 V (3.13%)668.4 V35.67 V (5.17%)6553.8 WDrop High
10 mm²57 A44 A12.97 V (1.88%)677.0 V21.4 V (3.1%)3932.2 WDrop High
16 mm²76 A59 A8.11 V (1.18%)681.9 V13.37 V (1.94%)2457.7 WDrop High
25 mm²101 A78 A5.19 V (0.75%)684.8 V8.56 V (1.24%)1572.9 WDrop High
35 mm²125 A97 A3.71 V (0.54%)686.3 V6.11 V (0.89%)1123.5 WDrop High
50 mm²151 A118 A2.59 V (0.38%)687.4 V4.28 V (0.62%)786.5 WDrop High
70 mm²192 A150 A1.85 V (0.27%)688.1 V3.06 V (0.44%)561.8 W✓ OK (≤3%)
95 mm²232 A181 A1.37 V (0.2%)688.6 V2.25 V (0.33%)413.9 W✓ OK (≤3%)
120 mm²269 A210 A1.08 V (0.16%)688.9 V1.78 V (0.26%)327.7 W✓ OK (≤3%)
150 mm²309 A241 A0.86 V (0.13%)689.1 V1.43 V (0.21%)262.1 W✓ OK (≤3%)
185 mm²353 A275 A0.7 V (0.1%)689.3 V1.16 V (0.17%)212.6 W✓ OK (≤3%)
240 mm²415 A324 A0.54 V (0.08%)689.5 V0.89 V (0.13%)163.8 W✓ OK (≤3%)
300 mm²477 A372 A0.43 V (0.06%)689.6 V0.71 V (0.1%)131.1 W✓ OK (≤3%)
400 mm²570 A445 A0.32 V (0.05%)689.7 V0.53 V (0.08%)98.3 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 175A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 175A over 20m at 690V (voltage drop: 1.85V or 0.27%).

What is the power capacity of 175A at 690V?

At unity power factor, 175A at 690V supports 209.15 kW with a standard 175A circuit breaker.