175 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 20.48V (2.97%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 17.35V (2.51%)
Voltage at Load669.5 VLine Loss: 6208.8 W
Max Power & Breaker209.15 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1297.31 V (188.02%)0.0 V2139.95 V (310.14%)393225.0 WDrop High
2.5 mm²24 A18 A778.38 V (112.81%)0.0 V1283.97 V (186.08%)235935.0 WDrop High
4 mm²32 A25 A486.49 V (70.51%)203.5 V802.48 V (116.3%)147459.4 WDrop High
6 mm²41 A32 A324.33 V (47.0%)365.7 V534.99 V (77.53%)98306.2 WDrop High
10 mm²57 A44 A194.6 V (28.2%)495.4 V320.99 V (46.52%)58983.8 WDrop High
16 mm²76 A59 A121.62 V (17.63%)568.4 V200.62 V (29.08%)36864.8 WDrop High
25 mm²101 A78 A77.84 V (11.28%)612.2 V128.4 V (18.61%)23593.5 WDrop High
35 mm²125 A97 A55.6 V (8.06%)634.4 V91.71 V (13.29%)16852.5 WDrop High
50 mm²151 A118 A38.92 V (5.64%)651.1 V64.2 V (9.3%)11796.7 WDrop High
70 mm²192 A150 A27.8 V (4.03%)662.2 V45.86 V (6.65%)8426.2 W~ ≤5%
95 mm²232 A181 A20.48 V (2.97%)669.5 V33.79 V (4.9%)6208.8 W✓ OK (≤3%)
120 mm²269 A210 A16.22 V (2.35%)673.8 V26.75 V (3.88%)4915.3 W✓ OK (≤3%)
150 mm²309 A241 A12.97 V (1.88%)677.0 V21.4 V (3.1%)3932.2 W✓ OK (≤3%)
185 mm²353 A275 A10.52 V (1.52%)679.5 V17.35 V (2.51%)3188.3 W✓ OK (≤3%)
240 mm²415 A324 A8.11 V (1.18%)681.9 V13.37 V (1.94%)2457.7 W✓ OK (≤3%)
300 mm²477 A372 A6.49 V (0.94%)683.5 V10.7 V (1.55%)1966.1 W✓ OK (≤3%)
400 mm²570 A445 A4.86 V (0.71%)685.1 V8.02 V (1.16%)1474.6 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 175A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 175A over 300m at 690V (voltage drop: 20.48V or 2.97%).

What is the power capacity of 175A at 690V?

At unity power factor, 175A at 690V supports 209.15 kW with a standard 175A circuit breaker.