175 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 1.31V (2.73%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.81V (22.52%)
Voltage at Load46.7 VLine Loss: 229.4 W
Max Power & Breaker8.4 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1747.67 V (3640.97%)0.0 V2882.83 V (6005.9%)305841.7 WDrop High
2.5 mm²24 A18 A1048.6 V (2184.58%)0.0 V1729.7 V (3603.54%)183505.0 WDrop High
4 mm²32 A25 A655.37 V (1365.36%)0.0 V1081.06 V (2252.21%)114690.6 WDrop High
6 mm²41 A32 A436.92 V (910.24%)0.0 V720.71 V (1501.48%)76460.4 WDrop High
10 mm²57 A44 A262.15 V (546.15%)0.0 V432.42 V (900.89%)45876.2 WDrop High
16 mm²76 A59 A163.84 V (341.34%)0.0 V270.27 V (563.05%)28672.7 WDrop High
25 mm²101 A78 A104.86 V (218.46%)0.0 V172.97 V (360.35%)18350.5 WDrop High
35 mm²125 A97 A74.9 V (156.04%)0.0 V123.55 V (257.4%)13107.5 WDrop High
50 mm²151 A118 A52.43 V (109.23%)0.0 V86.48 V (180.18%)9175.2 WDrop High
70 mm²192 A150 A37.45 V (78.02%)10.6 V61.77 V (128.7%)6553.7 WDrop High
95 mm²232 A181 A27.59 V (57.49%)20.4 V45.52 V (94.83%)4829.1 WDrop High
120 mm²269 A210 A21.85 V (45.51%)26.2 V36.04 V (75.07%)3823.0 WDrop High
150 mm²309 A241 A17.48 V (36.41%)30.5 V28.83 V (60.06%)3058.4 WDrop High
185 mm²353 A275 A14.17 V (29.52%)33.8 V23.37 V (48.7%)2479.8 WDrop High
240 mm²415 A324 A10.92 V (22.76%)37.1 V18.02 V (37.54%)1911.5 WDrop High
300 mm²477 A372 A8.74 V (18.2%)39.3 V14.41 V (30.03%)1529.2 WDrop High
400 mm²570 A445 A6.55 V (13.65%)41.4 V10.81 V (22.52%)1146.9 WDrop High

FAQ — 175 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 175A at 350 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 175A over 350m at 48V (voltage drop: 1.31V or 2.73%).

What is the power capacity of 175A at 48V?

At unity power factor, 175A at 48V supports 8.4 kW with a standard 175A circuit breaker.