⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.25V (2.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.54V (3.22%)
Voltage at Load46.8 VLine Loss: 31.2 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A249.67 V (520.14%)0.0 V411.83 V (857.99%)6241.7 WDrop High
2.5 mm²24 A18 A149.8 V (312.08%)0.0 V247.1 V (514.79%)3745.0 WDrop High
4 mm²32 A25 A93.62 V (195.05%)0.0 V154.44 V (321.74%)2340.6 WDrop High
6 mm²41 A32 A62.42 V (130.03%)0.0 V102.96 V (214.5%)1560.4 WDrop High
10 mm²57 A44 A37.45 V (78.02%)10.6 V61.77 V (128.7%)936.2 WDrop High
16 mm²76 A59 A23.41 V (48.76%)24.6 V38.61 V (80.44%)585.2 WDrop High
25 mm²101 A78 A14.98 V (31.21%)33.0 V24.71 V (51.48%)374.5 WDrop High
35 mm²125 A97 A10.7 V (22.29%)37.3 V17.65 V (36.77%)267.5 WDrop High
50 mm²151 A118 A7.49 V (15.6%)40.5 V12.35 V (25.74%)187.2 WDrop High
70 mm²192 A150 A5.35 V (11.15%)42.6 V8.82 V (18.39%)133.7 WDrop High
95 mm²232 A181 A3.94 V (8.21%)44.1 V6.5 V (13.55%)98.6 WDrop High
120 mm²269 A210 A3.12 V (6.5%)44.9 V5.15 V (10.72%)78.0 WDrop High
150 mm²309 A241 A2.5 V (5.2%)45.5 V4.12 V (8.58%)62.4 WDrop High
185 mm²353 A275 A2.02 V (4.22%)46.0 V3.34 V (6.96%)50.6 W~ ≤5%
240 mm²415 A324 A1.56 V (3.25%)46.4 V2.57 V (5.36%)39.0 W~ ≤5%
300 mm²477 A372 A1.25 V (2.6%)46.8 V2.06 V (4.29%)31.2 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (1.95%)47.1 V1.54 V (3.22%)23.4 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 350 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 25A over 350m at 48V (voltage drop: 1.25V or 2.6%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.