175 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 9.73V (2.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (3.87%)
Voltage at Load405.3 VLine Loss: 2949.2 W
Max Power & Breaker125.79 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2594.61 V (625.21%)0.0 V4279.9 V (1031.3%)786450.0 WDrop High
2.5 mm²24 A18 A1556.77 V (375.12%)0.0 V2567.94 V (618.78%)471870.0 WDrop High
4 mm²32 A25 A972.98 V (234.45%)0.0 V1604.96 V (386.74%)294918.8 WDrop High
6 mm²41 A32 A648.65 V (156.3%)0.0 V1069.97 V (257.83%)196612.5 WDrop High
10 mm²57 A44 A389.19 V (93.78%)25.8 V641.98 V (154.7%)117967.5 WDrop High
16 mm²76 A59 A243.24 V (58.61%)171.8 V401.24 V (96.68%)73729.7 WDrop High
25 mm²101 A78 A155.68 V (37.51%)259.3 V256.79 V (61.88%)47187.0 WDrop High
35 mm²125 A97 A111.2 V (26.79%)303.8 V183.42 V (44.2%)33705.0 WDrop High
50 mm²151 A118 A77.84 V (18.76%)337.2 V128.4 V (30.94%)23593.5 WDrop High
70 mm²192 A150 A55.6 V (13.4%)359.4 V91.71 V (22.1%)16852.5 WDrop High
95 mm²232 A181 A40.97 V (9.87%)374.0 V67.58 V (16.28%)12417.6 WDrop High
120 mm²269 A210 A32.43 V (7.82%)382.6 V53.5 V (12.89%)9830.6 WDrop High
150 mm²309 A241 A25.95 V (6.25%)389.1 V42.8 V (10.31%)7864.5 WDrop High
185 mm²353 A275 A21.04 V (5.07%)394.0 V34.7 V (8.36%)6376.6 WDrop High
240 mm²415 A324 A16.22 V (3.91%)398.8 V26.75 V (6.45%)4915.3 W~ ≤5%
300 mm²477 A372 A12.97 V (3.13%)402.0 V21.4 V (5.16%)3932.2 W~ ≤5%
400 mm²570 A445 A9.73 V (2.34%)405.3 V16.05 V (3.87%)2949.2 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 175A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 175A over 600m at 415V (voltage drop: 9.73V or 2.34%).

What is the power capacity of 175A at 415V?

At unity power factor, 175A at 415V supports 125.79 kW with a standard 175A circuit breaker.