175 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 600 m (1968.5 ft).
Copper Cable (≤3% Drop)400 mm²Drop: 9.73V (2.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (3.87%)
Voltage at Load405.3 VLine Loss: 2949.2 W
Max Power & Breaker125.79 kW175A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2594.61 V (625.21%) | 0.0 V | 4279.9 V (1031.3%) | 786450.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1556.77 V (375.12%) | 0.0 V | 2567.94 V (618.78%) | 471870.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 972.98 V (234.45%) | 0.0 V | 1604.96 V (386.74%) | 294918.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 648.65 V (156.3%) | 0.0 V | 1069.97 V (257.83%) | 196612.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 389.19 V (93.78%) | 25.8 V | 641.98 V (154.7%) | 117967.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 243.24 V (58.61%) | 171.8 V | 401.24 V (96.68%) | 73729.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 155.68 V (37.51%) | 259.3 V | 256.79 V (61.88%) | 47187.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 111.2 V (26.79%) | 303.8 V | 183.42 V (44.2%) | 33705.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 77.84 V (18.76%) | 337.2 V | 128.4 V (30.94%) | 23593.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 55.6 V (13.4%) | 359.4 V | 91.71 V (22.1%) | 16852.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 40.97 V (9.87%) | 374.0 V | 67.58 V (16.28%) | 12417.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 32.43 V (7.82%) | 382.6 V | 53.5 V (12.89%) | 9830.6 W | Drop High |
| 150 mm² | 309 A | 241 A | 25.95 V (6.25%) | 389.1 V | 42.8 V (10.31%) | 7864.5 W | Drop High |
| 185 mm² | 353 A | 275 A | 21.04 V (5.07%) | 394.0 V | 34.7 V (8.36%) | 6376.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 16.22 V (3.91%) | 398.8 V | 26.75 V (6.45%) | 4915.3 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 12.97 V (3.13%) | 402.0 V | 21.4 V (5.16%) | 3932.2 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 9.73 V (2.34%) | 405.3 V | 16.05 V (3.87%) | 2949.2 W | ✓ OK (≤3%) |
FAQ — 175 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 175A at 600 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 175A over 600m at 415V (voltage drop: 9.73V or 2.34%).
What is the power capacity of 175A at 415V?
At unity power factor, 175A at 415V supports 125.79 kW with a standard 175A circuit breaker.
Related Lengths & Currents (415V)
175A · 5m (415V)175A · 10m (415V)175A · 15m (415V)175A · 20m (415V)175A · 25m (415V)175A · 30m (415V)175A · 35m (415V)175A · 40m (415V)175A · 45m (415V)175A · 50m (415V)175A · 60m (415V)175A · 70m (415V)10A · 600m (415V)16A · 600m (415V)20A · 600m (415V)25A · 600m (415V)32A · 600m (415V)40A · 600m (415V)50A · 600m (415V)63A · 600m (415V)80A · 600m (415V)100A · 600m (415V)125A · 600m (415V)160A · 600m (415V)200A · 600m (415V)