25 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 1.38V (2.87%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.13V (2.36%)
Voltage at Load46.6 VLine Loss: 34.4 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A32.1 V (66.88%)15.9 V52.95 V (110.31%)802.5 WDrop High
2.5 mm²24 A18 A19.26 V (40.12%)28.7 V31.77 V (66.19%)481.5 WDrop High
4 mm²32 A25 A12.04 V (25.08%)36.0 V19.86 V (41.37%)300.9 WDrop High
6 mm²41 A32 A8.03 V (16.72%)40.0 V13.24 V (27.58%)200.6 WDrop High
10 mm²57 A44 A4.81 V (10.03%)43.2 V7.94 V (16.55%)120.4 WDrop High
16 mm²76 A59 A3.01 V (6.27%)45.0 V4.96 V (10.34%)75.2 WDrop High
25 mm²101 A78 A1.93 V (4.01%)46.1 V3.18 V (6.62%)48.1 W~ ≤5%
35 mm²125 A97 A1.38 V (2.87%)46.6 V2.27 V (4.73%)34.4 W✓ OK (≤3%)
50 mm²151 A118 A0.96 V (2.01%)47.0 V1.59 V (3.31%)24.1 W✓ OK (≤3%)
70 mm²192 A150 A0.69 V (1.43%)47.3 V1.13 V (2.36%)17.2 W✓ OK (≤3%)
95 mm²232 A181 A0.51 V (1.06%)47.5 V0.84 V (1.74%)12.7 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (0.84%)47.6 V0.66 V (1.38%)10.0 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (0.67%)47.7 V0.53 V (1.1%)8.0 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (0.54%)47.7 V0.43 V (0.89%)6.5 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.42%)47.8 V0.33 V (0.69%)5.0 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.33%)47.8 V0.26 V (0.55%)4.0 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.25%)47.9 V0.2 V (0.41%)3.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 45 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 25A over 45m at 48V (voltage drop: 1.38V or 2.87%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.