200 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 10.81V (2.61%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 11.57V (2.79%)
Voltage at Load404.2 VLine Loss: 3745.0 W
Max Power & Breaker143.76 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (208.4%)0.0 V1426.63 V (343.77%)299600.0 WDrop High
2.5 mm²24 A18 A518.92 V (125.04%)0.0 V855.98 V (206.26%)179760.0 WDrop High
4 mm²32 A25 A324.33 V (78.15%)90.7 V534.99 V (128.91%)112350.0 WDrop High
6 mm²41 A32 A216.22 V (52.1%)198.8 V356.66 V (85.94%)74900.0 WDrop High
10 mm²57 A44 A129.73 V (31.26%)285.3 V213.99 V (51.57%)44940.0 WDrop High
16 mm²76 A59 A81.08 V (19.54%)333.9 V133.75 V (32.23%)28087.5 WDrop High
25 mm²101 A78 A51.89 V (12.5%)363.1 V85.6 V (20.63%)17976.0 WDrop High
35 mm²125 A97 A37.07 V (8.93%)377.9 V61.14 V (14.73%)12840.0 WDrop High
50 mm²151 A118 A25.95 V (6.25%)389.1 V42.8 V (10.31%)8988.0 WDrop High
70 mm²192 A150 A18.53 V (4.47%)396.5 V30.57 V (7.37%)6420.0 WDrop High
95 mm²232 A181 A13.66 V (3.29%)401.3 V22.53 V (5.43%)4730.5 W~ ≤5%
120 mm²269 A210 A10.81 V (2.61%)404.2 V17.83 V (4.3%)3745.0 W✓ OK (≤3%)
150 mm²309 A241 A8.65 V (2.08%)406.4 V14.27 V (3.44%)2996.0 W✓ OK (≤3%)
185 mm²353 A275 A7.01 V (1.69%)408.0 V11.57 V (2.79%)2429.2 W✓ OK (≤3%)
240 mm²415 A324 A5.41 V (1.3%)409.6 V8.92 V (2.15%)1872.5 W✓ OK (≤3%)
300 mm²477 A372 A4.32 V (1.04%)410.7 V7.13 V (1.72%)1498.0 W✓ OK (≤3%)
400 mm²570 A445 A3.24 V (0.78%)411.8 V5.35 V (1.29%)1123.5 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 200A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 200A over 175m at 415V (voltage drop: 10.81V or 2.61%).

What is the power capacity of 200A at 415V?

At unity power factor, 200A at 415V supports 143.76 kW with a standard 200A circuit breaker.