⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 10.14V (2.44%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 10.7V (2.58%)
Voltage at Load404.9 VLine Loss: 438.9 W
Max Power & Breaker17.97 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A108.11 V (26.05%)306.9 V178.33 V (42.97%)4681.2 WDrop High
2.5 mm²24 A18 A64.87 V (15.63%)350.1 V107.0 V (25.78%)2808.7 WDrop High
4 mm²32 A25 A40.54 V (9.77%)374.5 V66.87 V (16.11%)1755.5 WDrop High
6 mm²41 A32 A27.03 V (6.51%)388.0 V44.58 V (10.74%)1170.3 WDrop High
10 mm²57 A44 A16.22 V (3.91%)398.8 V26.75 V (6.45%)702.2 W~ ≤5%
16 mm²76 A59 A10.14 V (2.44%)404.9 V16.72 V (4.03%)438.9 W✓ OK (≤3%)
25 mm²101 A78 A6.49 V (1.56%)408.5 V10.7 V (2.58%)280.9 W✓ OK (≤3%)
35 mm²125 A97 A4.63 V (1.12%)410.4 V7.64 V (1.84%)200.6 W✓ OK (≤3%)
50 mm²151 A118 A3.24 V (0.78%)411.8 V5.35 V (1.29%)140.4 W✓ OK (≤3%)
70 mm²192 A150 A2.32 V (0.56%)412.7 V3.82 V (0.92%)100.3 W✓ OK (≤3%)
95 mm²232 A181 A1.71 V (0.41%)413.3 V2.82 V (0.68%)73.9 W✓ OK (≤3%)
120 mm²269 A210 A1.35 V (0.33%)413.6 V2.23 V (0.54%)58.5 W✓ OK (≤3%)
150 mm²309 A241 A1.08 V (0.26%)413.9 V1.78 V (0.43%)46.8 W✓ OK (≤3%)
185 mm²353 A275 A0.88 V (0.21%)414.1 V1.45 V (0.35%)38.0 W✓ OK (≤3%)
240 mm²415 A324 A0.68 V (0.16%)414.3 V1.11 V (0.27%)29.3 W✓ OK (≤3%)
300 mm²477 A372 A0.54 V (0.13%)414.5 V0.89 V (0.21%)23.4 W✓ OK (≤3%)
400 mm²570 A445 A0.41 V (0.1%)414.6 V0.67 V (0.16%)17.6 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 25A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 25A over 175m at 415V (voltage drop: 10.14V or 2.44%).

What is the power capacity of 25A at 415V?

At unity power factor, 25A at 415V supports 17.97 kW with a standard 25A circuit breaker.