125 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 11.58V (2.79%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 11.15V (2.69%)
Voltage at Load403.4 VLine Loss: 2507.8 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A540.54 V (130.25%)0.0 V891.65 V (214.85%)117031.2 WDrop High
2.5 mm²24 A18 A324.33 V (78.15%)90.7 V534.99 V (128.91%)70218.7 WDrop High
4 mm²32 A25 A202.7 V (48.84%)212.3 V334.37 V (80.57%)43886.7 WDrop High
6 mm²41 A32 A135.14 V (32.56%)279.9 V222.91 V (53.71%)29257.8 WDrop High
10 mm²57 A44 A81.08 V (19.54%)333.9 V133.75 V (32.23%)17554.7 WDrop High
16 mm²76 A59 A50.68 V (12.21%)364.3 V83.59 V (20.14%)10971.7 WDrop High
25 mm²101 A78 A32.43 V (7.82%)382.6 V53.5 V (12.89%)7021.9 WDrop High
35 mm²125 A97 A23.17 V (5.58%)391.8 V38.21 V (9.21%)5015.6 WDrop High
50 mm²151 A118 A16.22 V (3.91%)398.8 V26.75 V (6.45%)3510.9 W~ ≤5%
70 mm²192 A150 A11.58 V (2.79%)403.4 V19.11 V (4.6%)2507.8 W✓ OK (≤3%)
95 mm²232 A181 A8.53 V (2.06%)406.5 V14.08 V (3.39%)1847.9 W✓ OK (≤3%)
120 mm²269 A210 A6.76 V (1.63%)408.2 V11.15 V (2.69%)1462.9 W✓ OK (≤3%)
150 mm²309 A241 A5.41 V (1.3%)409.6 V8.92 V (2.15%)1170.3 W✓ OK (≤3%)
185 mm²353 A275 A4.38 V (1.06%)410.6 V7.23 V (1.74%)948.9 W✓ OK (≤3%)
240 mm²415 A324 A3.38 V (0.81%)411.6 V5.57 V (1.34%)731.4 W✓ OK (≤3%)
300 mm²477 A372 A2.7 V (0.65%)412.3 V4.46 V (1.07%)585.2 W✓ OK (≤3%)
400 mm²570 A445 A2.03 V (0.49%)413.0 V3.34 V (0.81%)438.9 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 125A over 175m at 415V (voltage drop: 11.58V or 2.79%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.