225 Amp Cable Size at 200 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 17.56V (2.54%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 18.34V (2.66%)
Voltage at Load672.4 VLine Loss: 6842.4 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (161.16%)0.0 V1834.24 V (265.83%)433350.0 WDrop High
2.5 mm²24 A18 A667.19 V (96.69%)22.8 V1100.55 V (159.5%)260010.0 WDrop High
4 mm²32 A25 A416.99 V (60.43%)273.0 V687.84 V (99.69%)162506.2 WDrop High
6 mm²41 A32 A277.99 V (40.29%)412.0 V458.56 V (66.46%)108337.5 WDrop High
10 mm²57 A44 A166.8 V (24.17%)523.2 V275.14 V (39.87%)65002.5 WDrop High
16 mm²76 A59 A104.25 V (15.11%)585.8 V171.96 V (24.92%)40626.6 WDrop High
25 mm²101 A78 A66.72 V (9.67%)623.3 V110.05 V (15.95%)26001.0 WDrop High
35 mm²125 A97 A47.66 V (6.91%)642.3 V78.61 V (11.39%)18572.1 WDrop High
50 mm²151 A118 A33.36 V (4.83%)656.6 V55.03 V (7.97%)13000.5 WDrop High
70 mm²192 A150 A23.83 V (3.45%)666.2 V39.31 V (5.7%)9286.1 WDrop High
95 mm²232 A181 A17.56 V (2.54%)672.4 V28.96 V (4.2%)6842.4 W✓ OK (≤3%)
120 mm²269 A210 A13.9 V (2.01%)676.1 V22.93 V (3.32%)5416.9 W✓ OK (≤3%)
150 mm²309 A241 A11.12 V (1.61%)678.9 V18.34 V (2.66%)4333.5 W✓ OK (≤3%)
185 mm²353 A275 A9.02 V (1.31%)681.0 V14.87 V (2.16%)3513.6 W✓ OK (≤3%)
240 mm²415 A324 A6.95 V (1.01%)683.1 V11.46 V (1.66%)2708.4 W✓ OK (≤3%)
300 mm²477 A372 A5.56 V (0.81%)684.4 V9.17 V (1.33%)2166.8 W✓ OK (≤3%)
400 mm²570 A445 A4.17 V (0.6%)685.8 V6.88 V (1.0%)1625.1 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 200 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 200 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 200m at 690V (voltage drop: 17.56V or 2.54%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.