225 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 3.95V (0.57%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 4.13V (0.6%)
Voltage at Load686.0 VLine Loss: 1539.5 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A250.19 V (36.26%)439.8 V412.7 V (59.81%)97503.8 WDrop High
2.5 mm²24 A18 A150.12 V (21.76%)539.9 V247.62 V (35.89%)58502.2 WDrop High
4 mm²32 A25 A93.82 V (13.6%)596.2 V154.76 V (22.43%)36563.9 WDrop High
6 mm²41 A32 A62.55 V (9.07%)627.5 V103.18 V (14.95%)24375.9 WDrop High
10 mm²57 A44 A37.53 V (5.44%)652.5 V61.91 V (8.97%)14625.6 WDrop High
16 mm²76 A59 A23.46 V (3.4%)666.5 V38.69 V (5.61%)9141.0 WDrop High
25 mm²101 A78 A15.01 V (2.18%)675.0 V24.76 V (3.59%)5850.2 WDrop High
35 mm²125 A97 A10.72 V (1.55%)679.3 V17.69 V (2.56%)4178.7 WDrop High
50 mm²151 A118 A7.51 V (1.09%)682.5 V12.38 V (1.79%)2925.1 WDrop High
70 mm²192 A150 A5.36 V (0.78%)684.6 V8.84 V (1.28%)2089.4 WDrop High
95 mm²232 A181 A3.95 V (0.57%)686.0 V6.52 V (0.94%)1539.5 W✓ OK (≤3%)
120 mm²269 A210 A3.13 V (0.45%)686.9 V5.16 V (0.75%)1218.8 W✓ OK (≤3%)
150 mm²309 A241 A2.5 V (0.36%)687.5 V4.13 V (0.6%)975.0 W✓ OK (≤3%)
185 mm²353 A275 A2.03 V (0.29%)688.0 V3.35 V (0.48%)790.6 W✓ OK (≤3%)
240 mm²415 A324 A1.56 V (0.23%)688.4 V2.58 V (0.37%)609.4 W✓ OK (≤3%)
300 mm²477 A372 A1.25 V (0.18%)688.7 V2.06 V (0.3%)487.5 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (0.14%)689.1 V1.55 V (0.22%)365.6 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 45m at 690V (voltage drop: 3.95V or 0.57%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.