225 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 5 m (16.4 ft).
Copper Cable (≤3% Drop)95 mm²Drop: 0.44V (0.06%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.46V (0.07%)
Voltage at Load689.6 VLine Loss: 171.1 W
Max Power & Breaker268.9 kW225A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 27.8 V (4.03%) | 662.2 V | 45.86 V (6.65%) | 10833.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 16.68 V (2.42%) | 673.3 V | 27.51 V (3.99%) | 6500.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 10.42 V (1.51%) | 679.6 V | 17.2 V (2.49%) | 4062.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 6.95 V (1.01%) | 683.1 V | 11.46 V (1.66%) | 2708.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 4.17 V (0.6%) | 685.8 V | 6.88 V (1.0%) | 1625.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 2.61 V (0.38%) | 687.4 V | 4.3 V (0.62%) | 1015.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 1.67 V (0.24%) | 688.3 V | 2.75 V (0.4%) | 650.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 1.19 V (0.17%) | 688.8 V | 1.97 V (0.28%) | 464.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 0.83 V (0.12%) | 689.2 V | 1.38 V (0.2%) | 325.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 0.6 V (0.09%) | 689.4 V | 0.98 V (0.14%) | 232.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 0.44 V (0.06%) | 689.6 V | 0.72 V (0.1%) | 171.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.35 V (0.05%) | 689.7 V | 0.57 V (0.08%) | 135.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.28 V (0.04%) | 689.7 V | 0.46 V (0.07%) | 108.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.23 V (0.03%) | 689.8 V | 0.37 V (0.05%) | 87.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.17 V (0.03%) | 689.8 V | 0.29 V (0.04%) | 67.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.14 V (0.02%) | 689.9 V | 0.23 V (0.03%) | 54.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.1 V (0.02%) | 689.9 V | 0.17 V (0.02%) | 40.6 W | ✓ OK (≤3%) |
FAQ — 225 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 225A at 5 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 5m at 690V (voltage drop: 0.44V or 0.06%).
What is the power capacity of 225A at 690V?
At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.
Related Lengths & Currents (690V)
225A · 10m (690V)225A · 15m (690V)225A · 20m (690V)225A · 25m (690V)225A · 30m (690V)225A · 35m (690V)225A · 40m (690V)225A · 45m (690V)225A · 50m (690V)225A · 60m (690V)225A · 70m (690V)10A · 5m (690V)16A · 5m (690V)20A · 5m (690V)25A · 5m (690V)32A · 5m (690V)40A · 5m (690V)50A · 5m (690V)63A · 5m (690V)80A · 5m (690V)100A · 5m (690V)125A · 5m (690V)160A · 5m (690V)200A · 5m (690V)