225 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 1.32V (0.19%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.38V (0.2%)
Voltage at Load688.7 VLine Loss: 513.2 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A83.4 V (12.09%)606.6 V137.57 V (19.94%)32501.2 WDrop High
2.5 mm²24 A18 A50.04 V (7.25%)640.0 V82.54 V (11.96%)19500.8 WDrop High
4 mm²32 A25 A31.27 V (4.53%)658.7 V51.59 V (7.48%)12188.0 WDrop High
6 mm²41 A32 A20.85 V (3.02%)669.2 V34.39 V (4.98%)8125.3 WDrop High
10 mm²57 A44 A12.51 V (1.81%)677.5 V20.64 V (2.99%)4875.2 WDrop High
16 mm²76 A59 A7.82 V (1.13%)682.2 V12.9 V (1.87%)3047.0 WDrop High
25 mm²101 A78 A5.0 V (0.73%)685.0 V8.25 V (1.2%)1950.1 WDrop High
35 mm²125 A97 A3.57 V (0.52%)686.4 V5.9 V (0.85%)1392.9 WDrop High
50 mm²151 A118 A2.5 V (0.36%)687.5 V4.13 V (0.6%)975.0 WDrop High
70 mm²192 A150 A1.79 V (0.26%)688.2 V2.95 V (0.43%)696.5 WDrop High
95 mm²232 A181 A1.32 V (0.19%)688.7 V2.17 V (0.31%)513.2 W✓ OK (≤3%)
120 mm²269 A210 A1.04 V (0.15%)689.0 V1.72 V (0.25%)406.3 W✓ OK (≤3%)
150 mm²309 A241 A0.83 V (0.12%)689.2 V1.38 V (0.2%)325.0 W✓ OK (≤3%)
185 mm²353 A275 A0.68 V (0.1%)689.3 V1.12 V (0.16%)263.5 W✓ OK (≤3%)
240 mm²415 A324 A0.52 V (0.08%)689.5 V0.86 V (0.12%)203.1 W✓ OK (≤3%)
300 mm²477 A372 A0.42 V (0.06%)689.6 V0.69 V (0.1%)162.5 W✓ OK (≤3%)
400 mm²570 A445 A0.31 V (0.05%)689.7 V0.52 V (0.07%)121.9 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 15m at 690V (voltage drop: 1.32V or 0.19%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.