225 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 11.27V (2.72%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 11.46V (2.76%)
Voltage at Load403.7 VLine Loss: 4392.1 W
Max Power & Breaker161.73 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1389.97 V (334.93%)0.0 V2292.8 V (552.48%)541687.5 WDrop High
2.5 mm²24 A18 A833.98 V (200.96%)0.0 V1375.68 V (331.49%)325012.5 WDrop High
4 mm²32 A25 A521.24 V (125.6%)0.0 V859.8 V (207.18%)203132.8 WDrop High
6 mm²41 A32 A347.49 V (83.73%)67.5 V573.2 V (138.12%)135421.9 WDrop High
10 mm²57 A44 A208.5 V (50.24%)206.5 V343.92 V (82.87%)81253.1 WDrop High
16 mm²76 A59 A130.31 V (31.4%)284.7 V214.95 V (51.8%)50783.2 WDrop High
25 mm²101 A78 A83.4 V (20.1%)331.6 V137.57 V (33.15%)32501.2 WDrop High
35 mm²125 A97 A59.57 V (14.35%)355.4 V98.26 V (23.68%)23215.2 WDrop High
50 mm²151 A118 A41.7 V (10.05%)373.3 V68.78 V (16.57%)16250.6 WDrop High
70 mm²192 A150 A29.79 V (7.18%)385.2 V49.13 V (11.84%)11607.6 WDrop High
95 mm²232 A181 A21.95 V (5.29%)393.1 V36.2 V (8.72%)8553.0 WDrop High
120 mm²269 A210 A17.37 V (4.19%)397.6 V28.66 V (6.91%)6771.1 W~ ≤5%
150 mm²309 A241 A13.9 V (3.35%)401.1 V22.93 V (5.52%)5416.9 W~ ≤5%
185 mm²353 A275 A11.27 V (2.72%)403.7 V18.59 V (4.48%)4392.1 W✓ OK (≤3%)
240 mm²415 A324 A8.69 V (2.09%)406.3 V14.33 V (3.45%)3385.5 W✓ OK (≤3%)
300 mm²477 A372 A6.95 V (1.67%)408.1 V11.46 V (2.76%)2708.4 W✓ OK (≤3%)
400 mm²570 A445 A5.21 V (1.26%)409.8 V8.6 V (2.07%)2031.3 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 225A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 225A over 250m at 415V (voltage drop: 11.27V or 2.72%).

What is the power capacity of 225A at 415V?

At unity power factor, 225A at 415V supports 161.73 kW with a standard 225A circuit breaker.