⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 11.58V (1.68%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 19.11V (2.77%)
Voltage at Load678.4 VLine Loss: 501.6 W
Max Power & Breaker29.88 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.89 V (4.48%)659.1 V50.95 V (7.38%)1337.5 WDrop High
2.5 mm²24 A18 A18.53 V (2.69%)671.5 V30.57 V (4.43%)802.5 WDrop High
4 mm²32 A25 A11.58 V (1.68%)678.4 V19.11 V (2.77%)501.6 W✓ OK (≤3%)
6 mm²41 A32 A7.72 V (1.12%)682.3 V12.74 V (1.85%)334.4 W✓ OK (≤3%)
10 mm²57 A44 A4.63 V (0.67%)685.4 V7.64 V (1.11%)200.6 W✓ OK (≤3%)
16 mm²76 A59 A2.9 V (0.42%)687.1 V4.78 V (0.69%)125.4 W✓ OK (≤3%)
25 mm²101 A78 A1.85 V (0.27%)688.1 V3.06 V (0.44%)80.2 W✓ OK (≤3%)
35 mm²125 A97 A1.32 V (0.19%)688.7 V2.18 V (0.32%)57.3 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.13%)689.1 V1.53 V (0.22%)40.1 W✓ OK (≤3%)
70 mm²192 A150 A0.66 V (0.1%)689.3 V1.09 V (0.16%)28.7 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.07%)689.5 V0.8 V (0.12%)21.1 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.06%)689.6 V0.64 V (0.09%)16.7 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.04%)689.7 V0.51 V (0.07%)13.4 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.04%)689.7 V0.41 V (0.06%)10.8 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.03%)689.8 V0.32 V (0.05%)8.4 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.02%)689.8 V0.25 V (0.04%)6.7 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.02%)689.9 V0.19 V (0.03%)5.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 25A at 50 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 25A over 50m at 690V (voltage drop: 11.58V or 1.68%).

What is the power capacity of 25A at 690V?

At unity power factor, 25A at 690V supports 29.88 kW with a standard 25A circuit breaker.